Table of Contents Table of Contents
Previous Page  60 / 210 Next Page
Information
Show Menu
Previous Page 60 / 210 Next Page
Page Background

60

protection of DC circuits

DX

3

10000

voltage single pole

2P

3P

4P

Acc. to

IEC 60947-2

Icu

48 V

10 kA

10 kA

110 V

10 kA

10 kA

230 V

15 kA

DX

3

6000

voltage single pole

2P

3P

Acc. to

IEC 60947-2

Icu

48 V

6 kA

6 kA

110 V

6 kA

6 kA

230 V

DX

3

6000

voltage single pole

2P

3P

Acc. to

IEC 60947-2

Icu

48 V

6 kA

6 kA

110 V

6 kA

6 kA

230 V

Example : circuit earthed via the negative polarity / U = 110 V

=

/ Isc =

10 kA / In = 32 A

Protect the positive polarity using an MCB capable of breaking 10 kA

at 110 V (DX

3

10000 2P 32 A with 2 poles on the positive polarity)

For isolation, use a DX

3

10000 3P 32 A with 2 poles on the positive

polarity and one pole on the negative polarity

1 : MCB (U/2-Isc max.)

1

1

U/2

U/2

U-Isc max.

U/2-Isc max.

U/2-Isc max.

+

-

U-Isc max.

U-Isc max.

1

st

earth fault : I = O

2

nd

earth fault :

U and I Isc max.

U

+

-

1 : MCB (U-Isc max.)

1

1

Network earthed via a middle point:

Place on each polarity the number of poles necessary for max. Isc

breaking at half voltage

Example : circuit earthed via a middle point / U = 230 V

=

/ Isxc = 6 kA

/ In = 10 A

Protect each polarity using an MCB capable of breaking 6 kA at half

voltage, i.e. 115 V (DX

3

6000 4P 10 A with 2 poles on each polarity)

Isolated earth supply:

Distribute the poles necessary for breaking over the 2 polarities to

provide protection in the event of a double earth fault (particularly if

there are a number of circuits in parallel)

Example : isolated earth circuit / U = 48 V

=

/ Isc = 4 . 5 kA / In = 40 A

Protect the installation with an MCB capable of breaking 4 . 5 kA at

48 V and protect each polarity (DX

3

6000 MCB 2P 40 A with one pole

on each polarity)

Example : for a 110 V voltage,

use a 2 pole MCB and connect

the 2 poles in series

4 - Breaking capacity

For other voltages, the breaking capacities are as follows:

4000 A for a single pole MCB at max. voltage (80 V

=

per pole)

+

-

+

-

+

-

+

-

1 : Only if isolation required

MCB

(U-Isc max.)

U

U-Isc max

U=0

1

+

-

5 - Distribution of breaking poles

Place all the poles necessary for breaking on the other polarity

If isolation is required, an additional pole must be added on the

earthed polarity

Supply with one polarity earthed:

To choose the MCB and determine the pole distribution necessary

for breaking on each of the polarities, it is necessary to know how the

installation is earthed

DX

3

6000

voltage single pole

2P

3P

Acc. to

IEC 60947-2

Icu

48 V

6 kA

6 kA

110 V

6 kA

6 kA

230 V

Ics

1

48 V

100 % 100 %

110 V

100 % 100 %

230 V

DX

3

10000

voltage single pole

2P

3P

4P

Acc. to

IEC 60947-2

Icu

48 V

10 kA

10 kA

110 V

10 kA

10 kA

230 V

15 kA

Ics

1

48 V

100 % 100 %

110 V

100 % 100 %

230 V

100 %

1 : As a % of Icu

+

-

DX 10 A

4P

DX

3

6000

10 A 4P

DX 40 A

2P

+

-

DX

3

6 00

40 A 2P

DX-H 32 A

2P

DX-H 32 A

3P

If isolation required

+

+

-

-

3

10000

32 A 2P

3

10000

32 A 3P

n

Protection of DC circuits

DX

3

6000 and DX

3

10000 MCBs (1P/2P/3P/4P - In

63 A) designed for

use in 230/400 V

±

supplies, can also be used in DC circuits

In this case, the following deratings and precautions must be taken into

account

Max. magnetic tripping threshold : multiplied by 1. 4

Example : For a C curve MCB for which the AC tripping threshold is

between 5 and 10 In, the DC tripping threshold will be between

7 and 14 In

Max. operating voltage : 80 V per pole (60 V for single pole + N MCBs)

For voltages higher than this value, several poles must be wired in series

The time/current thermal tripping curve is the same as for AC

1 - Protection against short-circuits

2 - Protection against overloads

3 - Operating voltage