All dimensions (mm) are nominal

n

Tap-off boxes

With AC23A switch disconnector and fuse carrier,

125 A to 400 A : plug-in type

Specification

Rated insulating AC voltage

Ui (V)

1000

Rated impulse withstand voltage

Uimp (kV)

12

Type of rated duty

AC23A

Rated conditional short circuit current

(kA)

100

CEI EN 60947-3

85

540

340

320

260

550

20

Rear cable input

Can be installed and removed when the busbar is energized because

the protective earth makes contact before other conductors

To be applied on components with any rating, with tap-off outlets

For operating voltages (Ue) different from 400 V, please contact us on

+44 (0) 845 600 6266

Fuses not included. Please contact us on +44 (0) 845 600 6266 for

details of available fuses

Specification

Rated insulating AC voltage

Ui (V)

1000

Rated impulse withstand voltage

Uimp (kV)

12

Type of rated duty

AC23A

Rated conditional short circuit current

(kA)

100

CEI EN 60947-3

n

Bolt-on tap-off boxes

With AC23 switch disconnector and fuse carrier : 125 A to 1250 A

Dimensions of the box

Box rating

125 A to 400 A

630 A

800 A to 1250 A

(A) (mm)

365

400

450

(B) (mm)

630

750

1050

(C) (mm)

270

280

300

(D) (mm)

95

115

115

(E) (mm)

635

680

750

B

D

A

C

E

Please specify SCP type when ordering

Boxes cannot be installed simultaneously on both sides of the same

junction

For operating voltages (Ue) different from 400 V please contact us on

+44 (0) 845 600 6266

Fuses not included. Please contact us on +44 (0) 845 600 6266 for

details of available fuses

The bolted boxes are to be installed directly on the

junction when the busbar is disconnected and not

energized