CABLE MANAGEMENT

PERIMETER AND

DISTRIBUTION

PREMIER CABLE CAPACITY

TYPE OF

CONDUCTOR SIZE

CABLE

FACTOR

NBT3

(1)

NBT3TC

(3)

NBT3TC

(4)

NBT4

(2)

NBT4TC

(5)

NBT4TC

(6)

Full Term CSA 100% Fill (MM

2

)

1805

384

1383

3230

706

2455

TERM AT 45% FILL (MM

2

)

812

172

622

1453

317

1104

POWER CABLES

NUMBER OF CABLES AT 45% FILL

PVC

stranded

1.5mm

2

8.6

94

20

72

168

36

128

2.5mm

2

12.6

64

13

49

115

25

87

4mm

2

16.6

48

10

37

87

19

66

6mm

2

21.2

38

8

29

68

14

52

DATA CABLES

NUMBER OF CABLES AT 45% FILL (A) AND FULL CAPACITY (B)

A B A B A B A B A B A B

Cat 5E UTP 5.5mm dia.

30.2 26 59 5 12 20 45 48 106 10 23 36 81

Cat 5E STP 6.0mm dia.

36.0 22 50 4 10 17 38 40 89 8 19 30 68

Cat 6 UTP 6.5mm dia.

42.2 19 42 4 9 14 32 34 76 7 16 26 58

Cat 6 STP 7.0mm dia.

49.0 16 36 3 7 12 28 29 65 6 14 22 50

LIST NO.

COMPONENT DIMENSIONS

A

B

C

D

NBT3

240

170

125

125

NBT4

240

170

140

140

Norwich Technical

Components

The four components shown opposite are

fabricated sections and space must be allowed

for inclusion in runs of trunking. All other

components snap on over standard trunking

profiles.

The four components shown below are

fabricated sections and space must be allowed

for inclusion in runs of trunking.

All other components snap on over standard

trunking profiles.

A

B

B

B

FLAT TEE

FLAT ANGLE

C

C

D

D

EXTERNAL CORNER

INTERNAL CORNER

25

100 1

NBT3

40

100 2

NBT4

25

4

3

100

NBT3TC

40

6

5

100

NBT4TC

Note: NBT3 & NBT3TC are not deemed suitable for terminating Cat6 cabling.

Trunking

Dimensions (mm)