CIRCUIT PROTECTION
599
SINGLE-PHASE 230V TABLE
TYPE OF LIGHTING APPLICATION
(AC5A AND AC5B CATEGORIES)
6220S/6420S/
MAXIMUM NO. OF LAMPS
7440S
MAXIMUM NO. OF LAMPS
7263S
MAXIMUM NO. OF LAMPS
INCANDESCENT AND HALOGEN LAMPS
40W
57
115
172
60W
45
85
125
100W
28
70
100
HALOGEN LAMPS USED WITH TRANSFORMER
60W
14
27
40
80W
12
23
35
FLUORESCENT LAMP WITH STARTER (SINGLE FITTING WITH PARALLEL CORRECTION)
15W
20
40
60
20W
20
40
60
40W
20
40
60
FLUORESCENT LAMP WITH STARTER (SINGLE FITTING NON-CORRECTED)
15W
30
70
100
20W
30
70
100
40W
28
70
100
ELECTRONIC BALLAST (FLUORESCENT LAMP SINGLE SETTING)
18W
111
222
333
36W
58
117
176
ELECTRONIC COMPACT LAMP (LOW CONSUMPTION)
7W
200
400
600
11W
120
240
360
15W
88
176
264
20W
66
132
200
MOTORS – MAXIMUM POWER TYPE OF SMALL MOTOR APPLICATION (AC1 – AC7A CATEGORIES)
220/240V single phase with capacitor
400V three phase motor
1.2kW
3.2kW
5.5kW
12.5kW
8.5kW
15kW
HEATING – MAXIMUM POWER TYPE OF SMALL HEATING APPLICATION (AC7B CATEGORY)
NUMBER OF OPERATING CYCLES
230V SINGLE PH 400V 3 PH
230V SINGLE PH 400V 3 PH
230V SINGLE PH 400V 3 PH
100,000
5.4kW
16kW
8.6kW
26kW
13.6kW
41kW
150,000
4.6kW
14kW
7.4kW
22kW
11.6kW
35kW
200,000
3.5kW
10kW
5.6kW
17kW
8.8kW
26.5kW
500,000
1.6kW
5kW
2.6kW
7.5kW
4kW
12kW
1,000,000
1.2kW
3.5kW
1.9kW
6kW
3kW
9kW
ELECTRICAL ENDURANCE
AC1 and AC7a categories
250,000 operations
Sentry Technical
Applications and Maximum Ratings
LIGHTING – Maximum number of lamps
Presentation of installations according to type of supply.
The maximum number of lamps which can be operated per phase is equal to the total number of
lamps in the “Single-Phase 230V” table.
N
L1
230V
Single-phase circuit, 230V
3-phase circuit, 400V (with neutral)
L2
L1
230V
N
L3
230V
230V
Contactors