7

Switch Disconnectors

3NJ62 In-Line Switch Disconnectors with Fuses up to 630 A

Introduction

7/93

Siemens LV 10 · 2014

Main devices of sizes 2 and 3

1)

The fuse is available from Lawson Fuses (UK) and does not correspond to

BS 88.

Size

2

3

Switch disconnectors with fuses

type 3NJ62...

NH ...22-3

...22-4

...23-1

...24-1

...24-2

...23-3

...23-4

...32-3

...32-4

...33-1

...34-1

...34-2

...33-3

...33-4

BS ...82-3

...82-4

...83-3

...83-4

...92-3

...92-4

...94-1

...94-2

...93-3

...93-4

...33-3

...33-4

Breaking capacity

H

S

H

H

S

H

Rated insulation voltage

U

i

V 1000

Rated impulse withstand voltage

U

imp

V 8000

Rated operational current

I

e

• For fuse links

according to IEC 60269/ BS 88

A 400

630

500

630

500

For fuse links according to

IEC 60269

2 and 1

3 and 2

For BS fuse links acc. to BS 88

B4

3T

1)

Rated operational voltage

U

e

• At 50/60Hz rated frequency

V --

--

690

230

440

500

690

500

690

• At DC

V 230

440

--

--

--

--

--

--

--

Utilization category

DC23B DC21B AC22B AC23B DC23B DC21B AC22B

AC23B

Rated conditional short-circuit current

• Short-circuit strength (rms value)

kA 60

100

60

100

• Short-circuit making capacity

(rms value)

kA 60

55

66

60

55

66

Rated making capacity

• p.f. = 0.65

A --

--

1200 --

--

--

1890 1500 --

--

• p.f. = 0.45

A --

--

--

--

--

--

--

--

--

--

• p.f. = 0.35

A --

--

--

4000 --

--

--

--

6300 5000

Rated breaking capacity

• p.f. = 0.65

A --

--

1200 --

--

--

1890 1500 --

--

• p.f. = 0.45

A --

--

--

--

--

--

--

--

--

--

• p.f. = 0.35

A --

--

--

3200 --

--

--

--

5040 4000

Endurance

Operating cycles total

1000

1000

200

• Electrical (690 V, p.f. = 0.65)

200

Power loss

(no fuse links)

W 158

357

Permissible ambient temperature

°C -5...+55

Permissible mounting positions

Horizontal and vertical with bottom connection

Degree of protection

(in operating state)

IP41

Connection type

Main conductor connections

Cable lug connection

Conductor cross-section

• Conductor cross-section

(Al/Cu, solid or stranded) according to

DIN46235 (Cu) and DIN46239 (Al)

mm

2

1x 25-300

2x 25-240

1x 25-300

2x 25-240

• Screw size

2x M12

2x M12

30

• Torque

Nm 30

Terminal connection

• Conductor cross-section (Al/Cu), rm mm

2

2x 16-185

2x 16-185

• Conductor cross-section (Al/Cu), re mm

2

2x 16-150

2x 16-150

• Conductor cross-section (Al/Cu), sm mm

2

2x 35-240

2x 35-240

• Conductor cross-section (Al/Cu), se mm

2

2x 35-300

2x 35-300

• Required torque

Nm 25

25

© Siemens AG 2014