7
Switch Disconnectors
3NJ62 In-Line Switch Disconnectors with Fuses up to 630 A
Introduction
7/93
Siemens LV 10 · 2014
Main devices of sizes 2 and 3
1)
The fuse is available from Lawson Fuses (UK) and does not correspond to
BS 88.
Size
2
3
Switch disconnectors with fuses
type 3NJ62...
NH ...22-3
...22-4
...23-1
...24-1
...24-2
...23-3
...23-4
...32-3
...32-4
...33-1
...34-1
...34-2
...33-3
...33-4
BS ...82-3
...82-4
...83-3
...83-4
...92-3
...92-4
...94-1
...94-2
...93-3
...93-4
...33-3
...33-4
Breaking capacity
H
S
H
H
S
H
Rated insulation voltage
U
i
V 1000
Rated impulse withstand voltage
U
imp
V 8000
Rated operational current
I
e
• For fuse links
according to IEC 60269/ BS 88
A 400
630
500
630
500
For fuse links according to
IEC 60269
2 and 1
3 and 2
For BS fuse links acc. to BS 88
B4
3T
1)
Rated operational voltage
U
e
• At 50/60Hz rated frequency
V --
--
690
230
440
500
690
500
690
• At DC
V 230
440
--
--
--
--
--
--
--
Utilization category
DC23B DC21B AC22B AC23B DC23B DC21B AC22B
AC23B
Rated conditional short-circuit current
• Short-circuit strength (rms value)
kA 60
100
60
100
• Short-circuit making capacity
(rms value)
kA 60
55
66
60
55
66
Rated making capacity
• p.f. = 0.65
A --
--
1200 --
--
--
1890 1500 --
--
• p.f. = 0.45
A --
--
--
--
--
--
--
--
--
--
• p.f. = 0.35
A --
--
--
4000 --
--
--
--
6300 5000
Rated breaking capacity
• p.f. = 0.65
A --
--
1200 --
--
--
1890 1500 --
--
• p.f. = 0.45
A --
--
--
--
--
--
--
--
--
--
• p.f. = 0.35
A --
--
--
3200 --
--
--
--
5040 4000
Endurance
Operating cycles total
1000
1000
200
• Electrical (690 V, p.f. = 0.65)
200
Power loss
(no fuse links)
W 158
357
Permissible ambient temperature
°C -5...+55
Permissible mounting positions
Horizontal and vertical with bottom connection
Degree of protection
(in operating state)
IP41
Connection type
Main conductor connections
Cable lug connection
Conductor cross-section
• Conductor cross-section
(Al/Cu, solid or stranded) according to
DIN46235 (Cu) and DIN46239 (Al)
mm
2
1x 25-300
2x 25-240
1x 25-300
2x 25-240
• Screw size
2x M12
2x M12
30
• Torque
Nm 30
Terminal connection
• Conductor cross-section (Al/Cu), rm mm
2
2x 16-185
2x 16-185
• Conductor cross-section (Al/Cu), re mm
2
2x 16-150
2x 16-150
• Conductor cross-section (Al/Cu), sm mm
2
2x 35-240
2x 35-240
• Conductor cross-section (Al/Cu), se mm
2
2x 35-300
2x 35-300
• Required torque
Nm 25
25