Switch Disconnectors
3NJ62 In-Line Switch Disconnectors with Fuses up to 630 A
Introduction
7/92
Siemens LV 10 · 2014
7
■
Technical specifications
Main devices of sizes 00 and 1
1)
The fuse is available from Lawson Fuses (UK) and does not correspond to
BS 88.
Size
00
1
Switch disconnectors with fuses
type 3NJ62...
NH
...02-3
...02-4
...03-1
...04-1
...04-2
...03-3
...03-4
...12-3
...12-4
...13-1
...14-1
...14-2
...13-3
...13-4
BS ...43-3 ...53-3 ...62-3
...62-4
...63-3
...63-4
...72-3
...72-4
...74-1
...74-2
...73-3
...73-4
Breaking capacity
H H H
S
H
H
S
H
Rated insulation voltage
U
i
V 1000
Rated impulse withstand voltage
U
imp
V 8000
Rated operational current
I
e
A 63
100 160 -
160 125 160 125 250
For LV HRC fuse links
acc. to IEC 60269
-
-
00 and 000
1
For BS fuse links acc. to BS 88
A3
A3
00T
1)
B2
Rated operational voltage
U
e
• At 50/60Hz rated frequency
V 690
--
--
500 690 500 690 690
• At DC
V --
--
230 440 --
--
--
--
230 440 -
-
Utilization category
AC23B
DC23B DC21B AC22B
AC23B
DC23B DC21B AC22B AC23B
Rated conditional short-circuit current
• Short-circuit strength (rms value)
kA 100
60
100
100
60
100
• Short-circuit making capacity
(rms value)
kA 66
60
55
66
60
55
66
Rated making capacity
• p.f. = 0.65
A --
--
--
--
480 375 --
--
--
--
750 --
• p.f. = 0.45
A 630 1000 --
--
--
--
--
--
--
--
--
--
• p.f. = 0.35
A --
--
--
--
--
--
1600 1250 --
--
--
2500
Rated breaking capacity
• p.f. = 0.65
A --
--
--
--
480 375 --
--
--
--
750 --
• p.f. = 0.45
A 504 800 --
--
--
--
--
--
--
--
--
--
• p.f. = 0.35
A --
--
--
--
--
--
1280 1000 --
--
--
2000
Endurance
Operating cycles total
2000
1600
1600
• Electrical (690 V, p.f. = 0.65)
300
200
200
Power loss
(no fuse links)
W 7
17
43
78
Permissible ambient temperature
°C -5...+55
Permissible mounting positions
Horizontal and vertical with bottom connection
Degree of protection
(in operating state)
IP41
Connection type
Main conductor connections
Cable lug connection
• Conductor cross-section
(Al/Cu, solid or stranded) according to
DIN 46235 (Cu) and DIN 46239 (Al)
mm
2
1x 10-95
2x 16-70
1x 25-240
2x 25-70
• Screw size
M8
M12
• Torque
Nm 15
30
Terminal connection
• Conductor cross-section (Al/Cu), rm mm
2
1x 10-50
1x 16-185
• Conductor cross-section (Al/Cu), re mm
2
1x 10-50
1x 16-150
• Conductor cross-section (Al/Cu), sm mm
2
1x 16-95
1x 35-240
• Conductor cross-section (Al/Cu), se mm
2
1x 16-95
1x 35-300
• Required torque
Nm 15
25
© Siemens AG 2014