Background Image
Table of Contents Table of Contents
Previous Page  42 / 98 Next Page
Information
Show Menu
Previous Page 42 / 98 Next Page
Page Background

4-pole

2/42

Siemens LV 10.1 · 2011

* You can order this quantity or a multiple thereof.

1)

Front busbar connection pieces are included in the scope of supply

and are to be fitted by the customer.

Communication:

• For accessories, see page 2/98.

• For more information see also chapters "Measuring Devices

and E-Counters" and "Software".

Type

Rated

current

I

n

Current

setting of the

inverse-time

delayed

overcurrent

releases "

L

"

I

R

Operating

current of the

instantaneous

short-circuit

releases "

I

"

I

i

Ground-fault

protection "

G

"

I

g

DT

I

cu

up to 55 kA at 415 V, standard switching capacity N

See "Overview".

Order No.

For price

see page

2/54

PU

(UNIT,

SET, M)

PS*/

P. unit

PG Weight

per PU

approx.

Order No. supplement

required,

see page 2/57

A

A

A

A

kg

4-pole, fixed-mounted, for system protection, 63 A to 1600 A,

electronic releases LING

ETU12, LING function for 4-wire three-phase systems

With adjustable overcurrent releases, adjustable short-circuit releases,

vectorial summation current, ground-fault delay t

g

= 0.1 ... 0.3 s, ground-fault protection (G) can be switched off

with overcurrent and short-circuit release in 4th pole (N), N protection = 50/100 %

VL160/3VL2

63

25 ... 63 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL27 06-1

@@

4

@

-....

1 1 unit 113 3.100

100

40 ... 100 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL27 10-1

@@

4

@

-....

1 1 unit 113 3.100

160

64 ... 160 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL27 16-1

@@

4

@

-....

1 1 unit 113 3.100

VL250/3VL3

200

80 ... 200 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL37 20-1

@@

4

@

-....

1 1 unit 113 3.300

250 100 ... 250 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL37 25-1

@@

4

@

-....

1 1 unit 113 3.300

VL400/3VL4 315 128 ... 315 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL47 31-1

@@

46-....

1 1 unit 113 7.600

400 160 ... 400 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL47 40-1

@@

46-....

1 1 unit 113 7.600

VL630/3VL5

630 252 ... 630 1.25 ... 10 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL57 63-1

@@

46-....

1 1 unit 113 11.700

VL800/3VL6

800 320 ... 800 1.25 ... 8 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL67 80-1

@@

46-....

1 1 unit 113 20.500

VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL77 10-1

@@

46-....

1 1 unit 113 33.500

1250 500 ... 1250 1.25 ... 11 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL77 12-1

@@

46-....

1 1 unit 113 33.500

VL1600/3VL8

1)

1600 640 ... 1600 1.25 ... 9 ×

I

n

0.6 ... 1 ×

I

n

, OFF B

3VL87 16-1

@@

40-....

1 1 unit 113 40.800

N

L

I

G

NSE0_00693

1.0

Alarm

Active

>1.05

X3

x

I

n

R

I

17

14

20

(S)

R

t

30

25

10

8

6

4

6

8

x

I

n

5 4

3

2

10

i

I

11

I

N

I

g

t

g

I

N

NSE0_02079

OFF

OFF

I

100%

50%

.5

.8

.7 .63

.9

.6

.45

.4

.95

2.5

1.25

1.5

.6/.1

1/.1

.6/.1

1/.1

.6/.3

1/.3

.6/.3

1/.3

>

Connection type can be selected by assignment of the 12th position of the Order No.

• Connection with box terminal

3

• Connection with screw terminal

6

>

• Without communication preparation

TN

• With communication preparation

NN