4-pole
2/46
Siemens LV 10.1 · 2011
* You can order this quantity or a multiple thereof.
1)
Front busbar connection pieces are included in the scope of supply
and are to be fitted by the customer.
Type
Rated
current
I
n
Current
setting of the
inverse-time
delayed
overcurrent
releases
"
L
"
I
R
Operating
current of the
instantaneous
short-circuit
releases "
I
"
I
i
S function
short-
circuit
protection
(short-time
delayed)
S
Ground-fault
protection
"
G
"
I
g
DT
I
cu
up to 55 kA at 415 V,
standard switching capacity N
see "Overview"
Order No.
Basic price
per PU
PU
(UNIT,
SET, M)
PS*/
P. unit
PG Weight
per PU
approx.
Order No. supple-
ment required,
see page 2/57
A
A
A
A
A
kg
4-pole, fixed-mounted, for system protection - generator protection,
63 A to 1600 A, electronic releases LSIG, LSING
LCD-ETU42, LSIG/LSING function for 4-wire three-phase systems and time-based discrimination
With adjustable overcurrent releases, adjustable short-circuit releases
Ground fault delay t
g
= 0.1 ... 0.5 s, short-circuit delay t
sd
= 0 ... 0.3 s
with overcurrent and short-circuit release in 4th pole (N), N protection = 50 ... 100 %, OFF
VL160/3VL2 63
25 ... 63 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL27 06-1CN4
@
-....
1 1 unit 113 3.100
100
40 ... 100 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL27 10-1CN4
@
-....
1 1 unit 113 3.100
160
64 ... 160 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL27 16-1CN4
@
-....
1 1 unit 113 3.100
VL250/3VL3 200
80 ... 200 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL37 20-1CN4
@
-....
1 1 unit 113 3.300
250 100 ... 250 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL37 25-1CN4
@
-....
1 1 unit 113 3.300
VL400/3VL4 315 128 ... 315 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL47 31-1CN46-....
1 1 unit 113 7.600
400 160 ... 400 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL47 40-1CN46-....
1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 1.25 ... 10 ×
I
n
1.5 ... 9x
I
R
0.4 ... 1 ×
I
n
B
3VL57 63-1CN46-....
1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 1.25 ... 8 ×
I
n
1.5 ... 7x
I
R
0.4 ... 1 ×
I
n
B
3VL67 80-1CN46-....
1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL77 10-1CN46-....
1 1 unit 113 33.500
1250 500 ... 1250 1.25 ... 11 ×
I
n
1.5 ... 10x
I
R
0.4 ... 1 ×
I
n
B
3VL77 12-1CN46-....
1 1 unit 113 33.500
VL1600/3VL8
1)
1600 640 ... 1600 1.25 ... 9 ×
I
n
1.5 ... 8x
I
R
0.4 ... 1 ×
I
n
B
3VL87 16-1CN40-....
1 1 unit 113 40.800
N
L
S
I
G
NSE0_00697
CAT.A
25 CL
n
=250 A~
NSE-00547a
L3=179; N=0
L1=178; L2=181
ESC
>
Connection type can be selected by assignment of the 12th position of the Order No.
• Connection with box terminal
3
• Connection with screw terminal
6