IZM circuit-breakers, IN switch-disconnectors

Electronic releases for IZMX16 circuit-breakers

2010 CA08103002Z-EN

www.eaton.com

18/3

Electronic releases for IZMX16 circuit-breakers

IZMX16…A…

System protection

DTA

Digitrip 520

IZMX16…V…

Selectivity protection

DTV

Digitrip 520

IZMX16…U…

Universal protection

DTU

Digitrip 520M

Current range

200 A - 1600 A

200 A - 1600 A

200 A - 1600 A

RMS value monitoring

Protective functions

General

Ordering options

LI

LSI, LSIG

LSI, LSIG, LSIA

Rating plug (I

n

)

Overtemperature trip

Overload protection

L

Overload trip

(0.5 - 1.0) x I

n

(0.5 - 1.0) x I

n

(0.5 - 1.0) x I

n

Delay time I

2

t at 6 x I

r

2 - 24 s

2 - 24 s

2 - 24 s

Thermal memory

Short-time delayed short-circuit protection

S

Delayed short-circuit protection

-

(2 - 10) x I

r

(2 - 10) x I

r

Short delay time I

2

t at 8 x I

r

-

100 - 500 ms

100 - 500 ms

Short delay time, flat characteristic curve

-

100 - 500 ms

100 - 500 ms

Zone selectivity ZSI

1)

Non-delayed short-circuit protection

I

Non-delayed short-circuit protection

(2 - 10) x I

n

(2 - 12) x I

n

(2 - 12) x I

n

Switch-off function

Closing releases MCR

Optional ground fault protection

G

Ground/fault alarm

-

-

1)

Ground/fault protection release

-

(0.25 - 1.0) x I

n

3)

(0.25 - 1.0) x I

n

3)

Short delay time I

2

t at 0.625 x I

n

100 - 500 ms

100 - 500 ms

100 - 500 ms

Short delay time, flat characteristic curve

100 - 500 ms

100 - 500 ms

100 - 500 ms

Zone selectivity ZSI

1)

Thermal memory

Neutral conductor-conductor protection

N

System diagnostics

Status/Overload LED

-

Cause of trip LEDs

-

Current at trip point (display indication)

-

-

1

)

Ground fault release/alarm remote signaling (relay contact)

A

-

-

1)

Overload alarm monitoring

A

-

-

1)

System monitor

Digital display

-

-

4-digit LCD

Field bus communication

-

-

Optional: Modbus,

PROFIBUS

Additional functions

Test possibility

2)

-

Hand held test unit

Hand held test unit

Maintenance mode ARMS (Arc Flash Reduction Maintenance

System™)

-

-

1)

Notes

l

n

= rating plug (rate current module) = rated operational current current transformer

l

r

= Set value overload trip (= rated operational current of system)

1)

Requires external 24 V DC control voltage supply.

2)

Hand-held tester for simulating of secondary current

3)

In combination with ARMS function limited to 1200 A.

● Standard

○ Optional

IZMX16