Background Image
Table of Contents Table of Contents
Previous Page  27 / 164 Next Page
Information
Show Menu
Previous Page 27 / 164 Next Page
Page Background

WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION

PG00400018U – March 2012

27

Product overview

Memera consumer units and devices

1.4

Regulations

Relating to

Example

Additional Protection

411.3.3

All socket outlets up to 20A

– Upstairs sockets

30mA RCD

rating for general use by

– Downstairs sockets

ordinary persons

– Kitchen sockets

– Cooker outlet with integral

13A socket outlet

– Plus any other sockets rated up to 20A

including garage sockets

701.411.3.3

All electrical circuits in a room

– Shower circuit

30mA RCD

with a fixed bath or shower

– Lighting circuit

– Heating circuit

– Ventilation circuit

– Shaver socket

– Socket outlets

522.6.100

All electrical circuits buried in a

All concealed wiring

30mA RCD

522.6.101

wall or partition at less than

– Socket outlets

522.6.103

50mm and without mechanical

– Lighting circuits

protection

– Smoke alarm

– Burglar alarm

In summary

Installation design

The 17th edition wiring regulations BS7671 applies to all new installations designed after 30th June 2008, and there are

various options that must be considered in order to satisfy these requirements. Starting with the wiring scheme and the building design,

consideration must be given to the purpose of the building, and to the persons who will be using the installation, as different regulations

will be applicable, e.g. is the installation under the control of skilled or instructed persons, or ordinary persons, or perhaps the installed

location contains a bath or shower. Answers to these points will start to focus in on the regulations that need to be followed.

Consideration must be given to the way cables will be fitted within the installation, either on the surface in trunking or conduit, or else

concealed beneath the surface of the wall either buried within the plaster or inside the cavity of a hollow partition wall. The chosen

installation methods and wiring accessories or loads being fed, will also dictate whether additional protection by means of 30mA RCDs

is required on those circuits or not.

The wiring regulations are open to interpretation in some areas, where reference is made to “minimise inconvenience in the event of

a fault”, acceptable levels of inconvenience can be somewhat subjective.

In most circumstances the regulations now dictate that a consumer unit will be required to have two or more 30mA RCDs, enabling the

load circuits to be spread over a number of RCD protected zones or outgoing ways.

However, the most comprehensive and effective solution, and one that is guaranteed to fully meet the requirements of the regulations is

to equip each and every circuit with it’s own individual 30mA RCBO.

The examples shown on the next page illustrate just some of the many options available, to a contractor, to achieve a 17th Edition

compliant installation. Some options provide a much higher level of circuit integrity than others. The final choice of which may well be

made based on this and the cost/ease of the installation.