Background Image
Table of Contents Table of Contents
Previous Page  26 / 164 Next Page
Information
Show Menu
Previous Page 26 / 164 Next Page
Page Background

26

WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION

PG00400018U – March 2012

17th Edition regulations and consumer units

The advent of the 17th Edition of the Wiring regulations

brought with it new challenges for installers and manufacturers

alike, one such challenge involves the much greater use of

RCDs within the electrical installation. The regulations BS

7671:2008 now incorporate amendment No.1 2011.

Regulation 411.3.3.

States that additional protection by means of a 30mA RCD is

to be provided for all socket outlets with a rated current not

exceeding 20A for use by ordinary persons. The only exceptions

allowed are for socket outlets for use under the supervision

of “skilled” or “instructed persons” e.g. some commercial /

industrial locations, or a specific labelled socket provided for

connection of a particular item of equipment, e.g. a freezer circuit.

Regulation 701.411.3.3

In specific locations such as those containing a bath or shower

there is a requirement now to provide RCD protection on

all circuits, including the lighting and shower circuits.

Regulation 314.1 & 2

Requires that every installation shall be divided into circuits

as necessary to avoid danger and minimise inconvenience, in

the event of a fault. Also reducing the possibility of unwanted

RCD tripping, due to excessive protective conductor currents

but not due to an Earth fault. Separate circuits may be required

for parts of the installation, which need to be separately

controlled in such a way that they are not affected by the

failure of other circuits. The appropriate subdivision should

take account of any danger arising from the failure of a single

circuit eg. an RCD trip on a socket outlet causing the unwanted

failure of a lighting circuit and its associated hazards.

Regulation 522.6.102

Now requires a much greater use of RCDs to protect the

wiring concealed in walls or partitions even where installed in

previously defined “Safe Zones”. These regulations effectively

mean that all concealed wiring at a depth of less than 50mm

from the surface now requires protection by a 30mA RCD

unless provided with earthed mechanical protection.

Application of RCDs

The 17th Edition of the IEE wiring regulations ( BS7671 ),

detail a number of regulations relating to protection against

electric shock, including the need for additional protection.

The use of RCDs (Residual Current Devices) with a residual

operating current not exceeding 30mA is the recognised

means of providing this additional protection in the event

of failure of the provision for basic protection and or the

provision for fault protection or carelessness by users.

Such RCDs should not be used to provide the sole means of

protection and do not obviate the need to apply one or more of

the recognised protective measure as detailed in the regulations.

Under the new regulations an installation is required

to incorporate one or more RCDs, depending upon

the circumstances. Such instances include:-

• All socket outlets not exceeding 20A, but with certain

exceptions. One such exception would be permitted for a

specific labelled or otherwise suitably identified socket outlet

for connection of a particular piece of equipment.

• Mobile equipment with a current rating not exceeding 32A

for use outdoors

• Electrical circuits installed under “Special installations and

locations” as defined in Part 7 of the regulations e.g.

Swimming Pools / Saunas.

• All electrical circuits, including shower and lighting circuits

etc. in rooms with a fixed bath or shower e.g. bedrooms

and en-suite bathrooms.

In addition to the protection requirements of the

outgoing circuits / loads, the requirements of the

installed cabling also must be taken into account.

Where a cable is concealed in a wall or partition at a depth

of less than 50mm from the surface, even if installed in

the “safe zone”, if not provided with earthed mechanical

protection e.g. Metal trunking or conduit, it must be provided

with additional protection by means of a 30mA RCD.

Whilst it may be desirable to have one or two circuits fed via

an unprotected circuit e.g. an identified / dedicated freezer

circuit, the installation of the wiring may still dictate that the

circuit must be RCD protected. The protection of a circuit

by means of a 30mA RCD is also required where cables are

concealed in walls constructed with metal stud partitions

which are common in modern buildings, irrespective of the

depth from the surface, unless provided with protection

in the form of earthed metallic covering, trunking, conduit

or other mechanical protection so as to avoid damage to

the cable during installation or construction of the wall.

IEE Regulations and British Standards are subject to

amendments. This Eaton guide to consumer unit solutions is

not a substitute for the regulations which should always be

used for all types of electrical installations and design work.

Product overview

Memera consumer units and devices

1.4