Background Image
Table of Contents Table of Contents
Previous Page  58 / 133 Next Page
Information
Show Menu
Previous Page 58 / 133 Next Page
Page Background

CE I CON

C3 - C30 OV E R LOAD R E L AY S

1759

APPROX MOTOR APPROX MOTOR

kW

RATING

HP

RATING

Single Three

Single Three

Overload

C3-C7

C10-C19

C22-C30

phase

phase

phase

phase

relay

contactor

contactor

contactor

220/240

V 380/415V 220/240V 380/415V rating (A)

mounting

mounting

mounting

DIRECT-ON STARTING

LIST NO.

LIST NO.

LIST NO.

0.12

0.16

0.3–0.45

51500/

DC

0.18

0.25

0.45–0.67

51500/

EC

0.25

0.33

0.67–1.0

51500/

FC

0.06

0.37

0.08

0.5

1.0–1.5

51500/

GC

0.09

0.55

0.12

0.75

1.4–2.1

51500/

HC

0.12

0.75

0.16

1.0

1.8–2.7

51500/

IC

0.25

1.1

0.33

1.5

2.4–3.6

51500/

JC

0.37

1.5

0.50

2.0

3.5–5.0

51500/

KC

0.55

2.2

0.75

3.0

4.0–6.0

51500/

LC

0.75

4

1.0

5.5

5.5–8.5

51500/

MC

1.5

5.5

2.0

7.5

8.5–12.5

51500/

NC

0.06

0.08

0.15-0.25

55500/

BC

57500/

BC

0.12

0.16

0.24-0.40

55500/

CC

57500/

CC

0.18

0.25

0.38-0.63

55500/

DC

57500/

DC

0.25

0.33

0.6-1.0

55500/

FC

57500/

FC

0.06

0.55

0.08

0.75

0.96-1.6

55500/

GC

57500/

GC

0.09

1.1

0.12

1.5

1.5-2.5

55500/

HC

57500/

HC

0.37

1.5

0.50

2

2.4-4.0

55500/

JC

57500/

JC

0.75

2.2

1.0

3

3.8-6.3

55500/

KC

57500/

KC

1.1

4

1.5

5.5

6.0-10.0

55500/

MC

57500/

MC

2.2

7.5

3.0

10

9.6-16.0

55500/

NC

57500/

NC

3.7

11

5.0

15

15.0-25.0

57500/

PC

5.5

22

7.5

30

24.0-40.0

57500/

QC

3

11

4

15

13-21

3.7

12.5

5

17

16-25

4

15

5.5

20

21-32

5.5

22

7.5

30

25-40

7.5

25

10

34

32-50

30

40

50-63

STAR-DELTA STARTING

2.2

3

4.1-6.9

55500/

JC

57500/

JC

4

5.5

6.5-10.9

55500/

KC

57500/

KC

7.5

10

10.3-17.2

55500/

MC

57500/

MC

11

15

16.5-27.6

55500/

NC

57500/

NC

22

30

25.8-43.3

57500/

PC

37

50

41.5-69

57500/

QC

18.5

25

23-36

22

30

28-43

30

40

37-55

37

50

44-69

45

60

56-87

59

80

87-109

OVERLOAD RELAYS

l

Direct mounting onto appropriate contactor type.

Differential tripping mechanism.

Ambient temperature compensation.

Manual/Automatic reset facility.

Front mounted current adjustment dial.

Dimensions – see pages 260–261 Specification – see pages 241–242 Wiring diagrams – see pages 243–245 Tripping characteristics – see page 242