Background Image
Table of Contents Table of Contents
Previous Page  62 / 133 Next Page
Information
Show Menu
Previous Page 62 / 133 Next Page
Page Background

MANUAL MOTOR STARTERS

l

LIST No

Setting range

Operating current of

Rated ultimate short-circuit

short-circuit release

breaking capacity

(

A)

(

A)

(

IEC 947-2 EN 60947-2)

and Max. backup fuse

Icu (kA)/gL,aM(

Δ

)

230

V 400V 500V 690V

CMS25-0.16

0.1 - 0.16

1.9

CMS25-0.25

0.16 - 0.25

2.6

CMS25-0.4

0.25 - 0.4

4.4

CMS25-0.63

0.4 - 0.63

8

CMS25-1

0.63 - 1

11

CMS25-1.6

1 - 1.6

19

CMS25-2.5

1.6 - 2.5

30

3/25 2.5/20

CMS25-4

2.5 - 4

42

3/35 2.5/25

CMS25-6.3

4 - 6.3

69

3/50 2.5/35

CMS25-10

6.3 - 10

110

6/80 3/50 2.5/35

CMS25-16

10 - 16

210

6/80 4/80 2.5/63 2/35

CMS25-20

16 - 20

220

6/80 4/80 2.5/63 2/50

CMS25-25

20 - 25

330

6/80 4/80 2.5/63 2/50

MANUA L MOTOR S TAR T E R S

17583

ACCESSORIES

l

Auxiliary contacts

N/O

N/C

LIST No

2

0

CPS20

1

0

CPS10

0

1

CPS01

1

1

CPS11

Shunt Trip &

Undervoltage Release

Voltage 50Hz

Shunt Trip

UVR

24

CA24

CU24

48

CA48

CU48

110

CA110

CU110

230

CA230

CU230

400

CA400

CU400

IP55 ENCLOSURE

l

Note: Enclosure is supplied with IP55 membrane. In the case of an Emergency Stop or pad-

lock facility being fitted, IP rating will be IP40.

LIST No

CO–55

ENCLOSURE ACCESSORIES

l

LIST No

Emergency Stop Pushbutton

CNAT

Padlocking Device

CZ

Pushbuttons Membrane

CM

Additional Neutral/Earth link

CNL

Signal Lamp 230V Red

CSSR230

Dimensions – see page 262

CO–55

CNAT

CZ

CM

CNL

CSSR230

CA110

CU24

CPS11

CPS20

CMS25–6.3

CMS25–10

Switches are short-circuit

proof for any value of

prospective current

I

cc