MANUAL MOTOR STARTERS
l
LIST No
Setting range
Operating current of
Rated ultimate short-circuit
short-circuit release
breaking capacity
(
A)
(
A)
(
IEC 947-2 EN 60947-2)
and Max. backup fuse
Icu (kA)/gL,aM(
Δ
)
230
V 400V 500V 690V
CMS25-0.16
0.1 - 0.16
1.9
CMS25-0.25
0.16 - 0.25
2.6
CMS25-0.4
0.25 - 0.4
4.4
CMS25-0.63
0.4 - 0.63
8
CMS25-1
0.63 - 1
11
CMS25-1.6
1 - 1.6
19
CMS25-2.5
1.6 - 2.5
30
3/25 2.5/20
CMS25-4
2.5 - 4
42
3/35 2.5/25
CMS25-6.3
4 - 6.3
69
3/50 2.5/35
CMS25-10
6.3 - 10
110
6/80 3/50 2.5/35
CMS25-16
10 - 16
210
6/80 4/80 2.5/63 2/35
CMS25-20
16 - 20
220
6/80 4/80 2.5/63 2/50
CMS25-25
20 - 25
330
6/80 4/80 2.5/63 2/50
MANUA L MOTOR S TAR T E R S
17583
ACCESSORIES
l
Auxiliary contacts
N/O
N/C
LIST No
2
0
CPS20
1
0
CPS10
0
1
CPS01
1
1
CPS11
Shunt Trip &
Undervoltage Release
Voltage 50Hz
Shunt Trip
UVR
24
CA24
CU24
48
CA48
CU48
110
CA110
CU110
230
CA230
CU230
400
CA400
CU400
IP55 ENCLOSURE
l
Note: Enclosure is supplied with IP55 membrane. In the case of an Emergency Stop or pad-
lock facility being fitted, IP rating will be IP40.
LIST No
CO–55
ENCLOSURE ACCESSORIES
l
LIST No
Emergency Stop Pushbutton
CNAT
Padlocking Device
CZ
Pushbuttons Membrane
CM
Additional Neutral/Earth link
CNL
Signal Lamp 230V Red
CSSR230
Dimensions – see page 262
CO–55
CNAT
CZ
CM
CNL
CSSR230
CA110
CU24
CPS11
CPS20
CMS25–6.3
CMS25–10
Switches are short-circuit
proof for any value of
prospective current
I
cc