Background Image
Table of Contents Table of Contents
Previous Page  54 / 133 Next Page
Information
Show Menu
Previous Page 54 / 133 Next Page
Page Background

CE I CON

R E V E R S I NG S TAR T E R S E L ECT I ON GU I DE

175

REVERSING STARTERS

up to 40A

l

For example reversing direct-on starter, motor rating 4kW at 400/415V 3ph, contactor with 380/415V coil, enclosure with 3 push buttons & integral

motor circuit switch: overload relay

55500/

MC

,

contactor

53200/0

J

,

enclosure

55011/

AC0

.

Dimensions – see pages 260–261 Specification – see pages 241–242 Alternative coils – see page 181

Wiring diagrams – see page 244

Overload relay

Reversing contactor

Enclosure

Approx motor rating Full load

Coil

at 400/415V 3ph

current (A)

voltage

Push-button

kW HP

min–max LIST No

50

Hz

LIST No

arrangement LIST No

C10

24

V

53200/0

P

110

V

53200/0

M

230

V

53200/0

B

400

V

53200/0

J

C14

110

V

54200/0

M

230

V

54200/0

B

400

V

54200/0

J

C19

110

V

55200/0

M

230

V

55200/0

B

400

V

55200/0

J

C22

110

V

56200/0

M

230

V

56200/0

B

400

V

56200/0

J

C30

110

V

57200/0

M

230

V

57200/0

B

400

V

57200/0

J

0.06

0.08 0.15-0.25

55500/

BC

0.12

0.16 0.24-0.4

55500/

CC

0.18

0.25 0.38-0.63

55500/

DC

0.25

0.33 0.6-1

55500/

FC

0.55

0.75 0.96-1.6

55500/

GC

1.1

1.5

1.5-2.5

55500/

HC

1.5

2

2.4-4

55500/

JC

2.2

3

3.8-6.3

55500/

KC

4

5.5

6-10

55500/

MC

4

5.5

6–10

55500/

MC

5.5

7.5

6–10

55500/

MC

7.5

10

9.6–16

55500/

NC

11

15

15–25

57500/

PC

15

20

24–40

57500/

QC

I, II & 0

55001/

AB0

None

57001/

AB1

Reset only

57001/

AB2

I, II & 0

55011/

AC0

with

None

57011/

AC1

Motor Circuit

Reset only

57011/

AC2

Switch

I, II & 0

57001/

AB0

None

57001/

AB1

Reset only

57001/

AB2

I, II & 0

57011/

AC0

with

None

57011/

AC1

Motor Circuit

Reset only

57011/

AC2

Switch

55500/

MC

53200/0

J

55001/

AB0

55011/

AC0

1

Locate the kW, HP or Full Load Current of

the motor and select the overload relay.

2

Choose the contactor with the appropriate

coil voltage (alternative coils see page 181).

3

Choose the enclosure with the required pushbuttons

(

with or without MCS).

Enclosures: I, II & 0 versions supplied with separate legends FOR/REV, UP/DOWN, OPEN/CLOSE

C10-C30 are IP66, comprising Steel back box and Polycarbonate cover.