1/3
TSX 57 2
p
processors
TSX 57 3
p
processors
TSX 57 4
p
processors
TSX 57 5
p
processors
TSX 57 6
p
processors
8
with 4, 6, 8 or
12
slots
16
with 4, 6 or 8 slots or 8 with 12 slots
8
with 4, 6, 8 or
12
slots
16
with 4, 6 or 8 slots or 8 with 12 slots
1024
channels (8-, 16-, 32- or 64-channel module)
2048
channels (8-, 16-, 32- or 64-channel module)
80
channels (4-, 8- or 16- channel module) 128 channels (4-, 8- or 16-channel module) 256 channels (4-, 8- or 16- channel module) 512 channels (4-, 8- or 16- channel module)
18
24
32
18
64
Modules with 2/4 counter channels, single-channel electronic cam module
Modules with 2/4 counter channels, single-channel electronic cam module
–
Modules with 1/2 axes for stepper motors, 2/3/4 axes for analog
control servo motors, 8/16 axes with SERCOS digital link
–
Modules with 1/2 axes for stepper motors, 2/3/4 axes for analog
control servo motors, 8/16 axes with SERCOS digital link
Modules for 8 load cells (1 application-specific channel)
Modules for 8 load cells (1 application-specific channel)
TSX SCY in-rack communication modules (1 application-specific channel)
RS 232, RS 485 or current loop
(3)(4)
master/slave PCMCIAmodules and RS 485 in-rack master/slave communication modules
1
integrated RS 485 master/slave channel
(5)
,
RS 232, RS 485 or current loop
(3)(4)
master/slave PCMCIAmodules and RS 485 in-rack master/slave
communication modules
1
integrated RS 485 channel
(5)
,
RS 232, RS 485 or current loop
(3)(4)
PCMCIAmodules and RS 485 in-rack communication modules
–
4
in rack modules 8 in rack modules
–
8
in rack modules
–
1
PCMCIAmodule
(3)
–
1
PCMCIAmodule
(3)
–
1
in-rack module 3 in rack modules
–
4
in rack modules 5 in rack modules
2
2
3
4
In-rack modules: Ethernet Modbus/TCP (Web server, FactoryCast server or FactoryCast HMI server) and EtherNet/IP
–
Modbus Plus
(3)
,
Fipway
(3)(4)
modules,
Ethway in-rack modules
–
Modbus Plus
(3)
,
Fipway
(3)(4)(7)
modules
,
Ethway in-rack modules
10
channels with 3 loops max.
15
channels with 3 loops max.
20
channels with 3 loops max.
30
channels with 3 loops max.
Process control EFB library
Yes
–
Yes
–
160/192
Kb program and data
(8)
192/208
Kb program and data
(8)
440
Kb program and data
1
Mb program
and data
2
Mb program
and data
768
Kb program
160/192
Kb data
(8)
1.75
Mb program
192/208
Kb data
(8)
2
Mb program
440
Kb data
7
Mb program
1
Mb data
7
Mb program
2
Mb data
8
Mb (PCMCIA extension in upper or lower slot (0 or 1) on processor
–
1
100…240
V
a
, 24
V
c
non-isolated and 24…48 V
c
isolated power supply. A power supply is required for each rack.
See page 9/6
See pages 9/8 and 9/18
TSX P57 204M TSX P57 304M
TSX H57 24M
(10)
TSX P57 2634M TSX P57 3634M
g g g
TSX H57 44M
(10)
TSX P57 4634M TSX P57 5634M TSX P57 6634M
TSX P57 254M
g g
TSX P57 354M
TSX P57 454M
g g g g
TSX P57 554M
g g g g
4/60
1/10
4/60
1/11
(7)
TSX P57 46
34
M
/
5634
M/6634M
processors with integrated Ethernet port do not support the PCMCIA Fipway card.
(8)
The second value corresponds to
TSX P57 254M/354M
processors with integrated Fipio link and to the
TSX H57 24M
Hot Standby processor.
(9)
The integrated Ethernet port requires 1 of the available network connections.
(10)
The integrated Ethernet port is dedicated to Hot Standby communication (CPU Sync link between the “Primary” and “Standby” CPUs)
.
(11)
The
TSX P57 154M
processor does not support the CANopen bus PCMCIAmodule.
(12)
All processors in the Premium Unity range are equipped with 32-bit architecture microprocessors.
g g
g g g g
g g g
g g g g
2
1
3
4
5
6
7
8
9
10