Background Image
Table of Contents Table of Contents
Previous Page  9 / 413 Next Page
Information
Show Menu
Previous Page 9 / 413 Next Page
Page Background

1/3

TSX 57 2

p

processors

TSX 57 3

p

processors

TSX 57 4

p

processors

TSX 57 5

p

processors

TSX 57 6

p

processors

8

with 4, 6, 8 or

12

slots

16

with 4, 6 or 8 slots or 8 with 12 slots

8

with 4, 6, 8 or

12

slots

16

with 4, 6 or 8 slots or 8 with 12 slots

1024

channels (8-, 16-, 32- or 64-channel module)

2048

channels (8-, 16-, 32- or 64-channel module)

80

channels (4-, 8- or 16- channel module) 128 channels (4-, 8- or 16-channel module) 256 channels (4-, 8- or 16- channel module) 512 channels (4-, 8- or 16- channel module)

18

24

32

18

64

Modules with 2/4 counter channels, single-channel electronic cam module

Modules with 2/4 counter channels, single-channel electronic cam module

Modules with 1/2 axes for stepper motors, 2/3/4 axes for analog

control servo motors, 8/16 axes with SERCOS digital link

Modules with 1/2 axes for stepper motors, 2/3/4 axes for analog

control servo motors, 8/16 axes with SERCOS digital link

Modules for 8 load cells (1 application-specific channel)

Modules for 8 load cells (1 application-specific channel)

TSX SCY in-rack communication modules (1 application-specific channel)

RS 232, RS 485 or current loop

(3)(4)

master/slave PCMCIAmodules and RS 485 in-rack master/slave communication modules

1

integrated RS 485 master/slave channel

(5)

,

RS 232, RS 485 or current loop

(3)(4)

master/slave PCMCIAmodules and RS 485 in-rack master/slave

communication modules

1

integrated RS 485 channel

(5)

,

RS 232, RS 485 or current loop

(3)(4)

PCMCIAmodules and RS 485 in-rack communication modules

4

in rack modules 8 in rack modules

8

in rack modules

1

PCMCIAmodule

(3)

1

PCMCIAmodule

(3)

1

in-rack module 3 in rack modules

4

in rack modules 5 in rack modules

2

2

3

4

In-rack modules: Ethernet Modbus/TCP (Web server, FactoryCast server or FactoryCast HMI server) and EtherNet/IP

Modbus Plus

(3)

,

Fipway

(3)(4)

modules,

Ethway in-rack modules

Modbus Plus

(3)

,

Fipway

(3)(4)(7)

modules

,

Ethway in-rack modules

10

channels with 3 loops max.

15

channels with 3 loops max.

20

channels with 3 loops max.

30

channels with 3 loops max.

Process control EFB library

Yes

Yes

160/192

Kb program and data

(8)

192/208

Kb program and data

(8)

440

Kb program and data

1

Mb program

and data

2

Mb program

and data

768

Kb program

160/192

Kb data

(8)

1.75

Mb program

192/208

Kb data

(8)

2

Mb program

440

Kb data

7

Mb program

1

Mb data

7

Mb program

2

Mb data

8

Mb (PCMCIA extension in upper or lower slot (0 or 1) on processor

1

100…240

V

a

, 24

V

c

non-isolated and 24…48 V

c

isolated power supply. A power supply is required for each rack.

See page 9/6

See pages 9/8 and 9/18

TSX P57 204M TSX P57 304M

TSX H57 24M

(10)

TSX P57 2634M TSX P57 3634M

g g g

TSX H57 44M

(10)

TSX P57 4634M TSX P57 5634M TSX P57 6634M

TSX P57 254M

g g

TSX P57 354M

TSX P57 454M

g g g g

TSX P57 554M

g g g g

4/60

1/10

4/60

1/11

(7)

TSX P57 46

34

M

/

5634

M/6634M

processors with integrated Ethernet port do not support the PCMCIA Fipway card.

(8)

The second value corresponds to

TSX P57 254M/354M

processors with integrated Fipio link and to the

TSX H57 24M

Hot Standby processor.

(9)

The integrated Ethernet port requires 1 of the available network connections.

(10)

The integrated Ethernet port is dedicated to Hot Standby communication (CPU Sync link between the “Primary” and “Standby” CPUs)

.

(11)

The

TSX P57 154M

processor does not support the CANopen bus PCMCIAmodule.

(12)

All processors in the Premium Unity range are equipped with 32-bit architecture microprocessors.

g g

g g g g

g g g

g g g g

2

1

3

4

5

6

7

8

9

10