Background Image
Table of Contents Table of Contents
Previous Page  93 / 267 Next Page
Information
Show Menu
Previous Page 93 / 267 Next Page
Page Background

3VT2 Molded Case Circuit Breakers up to 250 A

Accessories and Components

Mounting accessories

Plug-in design

3/37

Siemens LV 36 · 2008

3

Design

Plug-in devices

3VT9 200-4PA30

Locking plug-in device against plug-in

device

inserting the circuit breaker

• The plug-in device includes complete accessories for assem-

bling a circuit breaker/switch disconnector in plug-in design

from the original fixed-mounted design

• The components of the plug-in device are:

- supporting part of the plug-in device 2 connection sets

(total of 6 terminals) for fitting on to the switching unit

- interlocking connecting rod (ensures automatic switching off

of the circuit breaker for handling – inserting and removal)

- set of mounting bolts for securing circuit breaker into plug-in

device (to secure plug-in device into switchboard, a set of

mounting bolts is used that is included in the scope of supply

of the 3VT2 725-.AA36-0AA0 switching unit.

Main circuit

• The 3VT9 200-4TA30

connecting set is used for connecting

with busbars or cable lugs and is included in the scope of sup-

ply of the 3VT9 275-.AA36-0AA0 switching unit

• For connecting in another way, it is necessary to use connect-

ing sets

(see page 3/9)

• The type of connections must comply with our recommenda-

tions

(see page 3/11)

.

Auxiliary circuits

These are connected using a 3VT9 300-4PL00 15-wire cable.

Coding

3VT9 200-4WN00 coding set

The plug-in device and circuit breaker can be provided with a

coding set, which prevents inserting any other circuit breaker

into the plug-in device.

Position signaling

3VT9 300-4WL00 position signaling switch

The plug-in device may be provided with a maximum of four

switches (for 4-pole version, max. 6 switches) for signaling the

connected/removed position.

States of 3VT9 300-4WL00 switches in the plug-in device

according to the circuit breaker position

0 = contact open, 1 = contact closed

1)

Accessory compartments 19 and 20 are for 4-pole version only.

Technical specifications

For wiring diagram of the circuit breaker in plug-in device with

accessories, see page 3/13.

Plug-in device with motorized operating mechanism

Circuit breaker in plug-in design with motorized operating mechanism

Accessory compartment

11 ... 14 (19, 20)

1)

Circuit breaker position

Connected

0

1

Removed

1

0

Order No.

3VT9 300-4WL00

Rated operational voltage U

e

V AC 400

AC 250

Rated isolation voltage U

i

V AC 500

Rated frequency f

n

Hz 50/60

Rated operational current

I

e

/U

e

• AC-13

3 A/400 V

• DC-15

0.15 A/250 V, 3 A/125 V, 4 A/30 V

Thermal current

I

th

A 6

Arrangement of contacts

001

Connector cross-section S

mm

2

0.5 ... 1

Terminal protection

(connected switch)

IP20

2

1

4