3VT2 Molded Case Circuit Breakers up to 250 A

Accessories and Components

Mounting accessories

Withdrawable design

3/40

Siemens LV 36 · 2008

3

With motorized operating mechanism

Recommended wiring

Description

Inserting and withdrawing the circuit breaker

with motorized operating mechanism

• Each time before inserting or withdrawing the circuit breaker,

we recommend first to turn the AUTO/MANUAL switch on the

motorized operating mechanism to the MANUAL position

• More operating information can be found in the operating

instructions

• Not adhering to this procedure or failing to follow the recom-

mended wiring, could mean that the circuit breaker will not

successfully switch on at the first attempt.

L+

Q3

X3

MP

NC NO

S5

C

X3

X4

PE

YC

N–

9 7

8

3

6

4

2

1

2

5

1

M P

NSO0_00208

S

B

Operating

counter

Motor drive

Motor drive control circuits

ON

OFF

Symbol

Description

MP

3VT9 300-3M..0 motorized operating mechanism

M

motor

P

storage device

X3

terminal strip to connect control circuits

X4

terminal strip for external operations counter

S5

switch indicating AUTO (NO-C)/MANUAL (NC-C) modes

YC

3VT9 300-3MF10 external operations counter

B

recommended wiring of the control circuits (control cir-

cuits not included in motorized operating mechanism

delivery)

ON

make pushbutton

OFF

break pushbutton

S

switch to store up energy

Q3

motorized operating mechanism circuit breaker for

AC 24 V LSN 4C/1

AC 48 V LSN 4C/1

AC 110 V LSN 4C/1

AC 230 V LSN 2C/1

DC 24 V LSN-DC 4C/1

DC 48 V LSN-DC 4C/1

DC 110 V LSN-DC 4C/1

DC 230 V LSN-DC 2C/1