Background Image
Table of Contents Table of Contents
Previous Page  92 / 267 Next Page
Information
Show Menu
Previous Page 92 / 267 Next Page
Page Background

3VT2 Molded Case Circuit Breakers up to 250 A

Accessories and Components

Mounting accessories

3/36

Siemens LV 36 · 2008

3

Overview

Plug-in devices

The plug-in design of the circuit breaker/switch disconnector is

intended for demanding industrial applications where rapid ex-

change of the circuit breaker along with both visual and conduc-

tive disconnection of the circuit is needed.

• The device includes:

- complete accessories for assembling circuit breakers/

switch disconnectors in plug-in design

- a set of four installation bolts (M4 x 40) for fixing the switching

unit to the plug-in device

• The device must be fitted with:

- a 3-pole 3VT2 725-.AA36-0AA0 switching unit or

- a 4-pole 3VT2 725-.AA46-0AA0 or 3VT2 725-.AA56-0AA0

switching unit

3VT9 200-4PA30 plug-in device

Circuit breaker position

The circuit breaker in plug-in design has two positions:

1.

connected (operating position)

2. removed

Circuit breaker accessories in plug-in design

The circuit breaker in plug-in design has the same accessories

as the fixed-mounted circuit breaker.

Advantages and enhanced safety for the operator

• Unambiguous remote signaling of the circuit breaker position

in the plug-in device

• Option to lock the plug-in device with padlocks to prevent in-

serting of the circuit breaker

• Visible and conductive disconnection of the power circuit

• Easy exchange of the circuit breaker in case of a failure

• IP20 degree of protection of all termination points

• The plug-in device does not need earthing.

Withdrawable devices

The withdrawable design of the circuit breaker/switch discon-

nector is intended for demanding industrial applications where

rapid exchange of the circuit breaker, frequent checking and

both visual and conductive disconnection of the circuit is

needed.

• The device includes complete accessories for assembling cir-

cuit breakers/switch disconnectors in withdrawable design

• The device must be fitted with

- a 3-pole 3VT2 725-.AA36-0AA0 switching unit or

- a 4-pole 3VT2 725-.AA56-0AA0 or 3VT2 725-.AA56-0AA0

switching unit.

3VT9 200-4WA30 withdrawable device

Circuit breaker position

The circuit breaker in withdrawable design has three positions:

1. connected (operating position)

2. withdrawn (maintenance position)

3. removed

Circuit breaker accessories in withdrawable design

The circuit breaker in withdrawable design has the same acces-

sories as the fixed-mounted circuit breaker.

Advantages and enhanced safety for the operator

• Unambiguous remote and local signaling of the circuit breaker

and arrestment positions in the withdrawable device

• Checking of circuit breaker and accessories function in the

maintenance position

• Locking of the withdrawable device with padlocks

- prevents inserting of the circuit breaker

- locking of circuit breaker in inserted (operating) position

- locking of circuit breaker in withdrawn (maintenance)

position

• Visible and conductive disconnection of the power circuit

• Easy exchange of circuit breakers in case of failure

• IP20 degree of protection of all termination points

• The withdrawable device does not need earthing.