3VT2 Molded Case Circuit Breakers up to 250 A

Accessories and Components

Motorized operating mechanism

3/34

Siemens LV 36 · 2008

3

Recommended actuating pulses

Circuit breaker switched on/off by the motorized operating

mechanism – S switch permanently closed (automatic storage)

or open

Circuit breaker switched off by the overcurrent or auxiliary

releases and switched on by the motorized operating mecha-

nism – S switch permanently closed (automatic storage)

Circuit breaker switched off by the overcurrent or auxiliary

releases and switched on by the motorized operating mecha-

nism – S switch closed only for storing up

Description of charts

Circuit breaker states and toggle positions of the circuit breakers

NSO0_00245

t

[ms]

1

0

1

0

1

0

HK

PS

400 …

800

800

20 … 700

> 100

> 1400

50

> 600

IMP OFF

IMP ON

NSO0_00246

t

[ms]

1

0

1

0

1

0

HK

RS

R

520

20 … 700

> 1400

50

> 880

OFF

IMP ON

NSO0_00247

t

[ms]

1

0

1

0

1

0

HK

RS

R

X + 520

20 … 700

> 1400

X

50

400 …

> 880

> 100

OFF

IMP ON

IMP S

Symbol

Description

HK

main contacts

PS

auxiliary switch

RS

relative switch

R OFF

circuit breaker closing instant by release

IMP S

pulse to store up motorized operating mechanism energy

(generated by S switch)

IMP ON

make pulse for motorized operating mechanism

IMP OFF

break pulse for motorized operating mechanism

X

random segment of time

Circuit breaker state

Toggle positions of circuit breakers

Switched on

Switched off by releases, or by TEST

button or by the trip pushbutton on

the motorized operating mechanism

Switched off manually or electrically

by the operating mechanism