3VT1 Molded Case Circuit Breakers up to 160 A

Circuit breakers · Switch disconnectors

2/19

Siemens LV 36 · 2008

2

Overcurrent releases, 4-pole version

The overcurrent release is an integral part of the circuit breaker.

It is not possible to deinstall or exchange the releases.

4-pole circuit breakers are manufactured in the following

versions:

• 3P+N (three poles protected, N-pole unprotected)

• 4P (all four poles protected)

The permissible load of the N-pole is 100%

I

n

.

Tripping characteristics

The circuit breakers are delivered with three types of tripping

characteristics designated by the following letters:

„L“ - lines

Protection of lines with low starting current

„D“ - distribution

Protection of lines and transformers

„N“ - short-circuit

Protection against short circuit only

• 3VT1 Circuit breakers with characteristic

„L“

have a fixed

value of rated current

I

(without

I

n

control). The circuit break-

ers are manufactured with

I

n

values of standard current range

40 ... 160 A, see „Ranges of overcurrent release and their

possible setting“. The Short-circuit release has a fixed setting

to 4 x

I

n

.

• 3VT1 circuit breakers with characteristic

„D“

can be set to a

reduced current in the range of approx. 0.75 ... 1

I

n

.

The circuit breakers are manufactured with

I

n

values within a

standard current range of 16 ... 160 A.

Setting values are given in the table on page 2/20.

• 3VT1 Circuit breakers with characteristic

„N“

have only a short

circuit release. They are manufactured with circuit breaker val-

ues within a standard current range of 32 ... 160 A. The Short

circuit release is adjustable.

The values are given in the table on page 2/20.

The type designation for the circuit breakers is set according

to the requested rated current and protection characteris-

tics.

For example.: Protection of a circuit with

I

n

= 40 A.

The order No. designation will be 3VT1 704-2EC46-0AA0.

Setting of tripping characteristics

Dependent release (thermal) L

(for circuit breakers with

characteristics “D” and “M”). The dependent release for over-

load protection

I

r

(instantaneous), is adjusted in a continuous

range using the

I

r

adjustment dial on the overload release. The

I

r

adjustment range is 0.75 ... 1

I

n

.

Independent instantaneous release (short-circuit relase) I

(for circuit breakers with characteristics “D” and “N”). With an

independent instantaneous release (value of the short circuit

current

I

i

), adjustment is possible within a continuous range.

All values are given in the table on page 2/20.

Setting of tripping characteristics

Circuit breakers with characteristic

„L“

„D“

„N“

NSO0_00502

t

I

L

I

NSO0_00500

t

I

L

I

I

r

I

i

NSO0_00216

t

I

L

I

I

i