Background Image
Table of Contents Table of Contents
Previous Page  26 / 267 Next Page
Information
Show Menu
Previous Page 26 / 267 Next Page
Page Background

3VT1 Molded Case Circuit Breakers up to 160 A

Circuit breakers · Switch disconnectors

2/16

Siemens LV 36 · 2008

2

„N“

Setting

I

R

and

I

i

for circuit breakers with characteristic „D“

Adjusting

I

R

Adjusting

I

i

Derating in accordance with ambient temperature

Current ranges of overcurrent releases and their possible setting at 40 °C

NSO0_00216

t

I

L

I

I

i

Rated

current

I

n

Permissible load

A

+ 55 °C

+ 40 °C +20 °C

-15 °C

16

15

16

17

19

20

19

20

22

25

25

23

25

28

31

32

29

32

36

41

40

38

40

45

53

50

48

50

56

66

63

57

63

69

83

80

73

80

88

100

100

91

100

105

122

125

110

125

132

145

Rated

current

I

n

3VT1 7..-2DA36-0AA0

3VT1 7..-2DC36-0AA0

3VT1 7..-2DM36-0AA0

3VT1 7..-2DB36-0AA0

Overload

protection

I

r

Short circuit

protection

I

i

(instantaneous)

Overload

protection

I

r

Short circuit

protection

I

i

(instantaneous)

Overload

protection

I

r

Short circuit

protection

I

i

(instantaneous)

Overload

protection

I

r

Short circuit

protection

I

i

(instantaneous)

A

A

A

A

A

A

A

A

A

16

--

--

12,5 ... 16

160 ... 240

12,5 ... 16

160

--

--

20

--

--

16 ... 20

200 ... 300

16 ... 20

200

--

--

25

--

--

20 ... 25

250 ... 375

20 ... 25

250

--

--

32

--

--

25 ... 32

160 ... 320

25 ... 32

320

--

160 ... 320

40

40

160

32 ... 40

200 ... 400

32 ... 40

400

--

200 ... 400

50

50

200

40 ... 50

250 ... 500

40 ... 50

500

--

250 ... 500

63

63

252

50 ... 63

315 ... 630

50 ... 63

630

--

315 ... 630

80

80

320

63 ... 80

400 ... 800

63 ... 80

800

--

400 ... 800

100

100

400

80 ... 100

500 ... 1000

80 ... 100

1000

--

500 ... 1000

125

125

500

100 ... 125

625 ... 1250

--

--

--

625 ... 1250

160

160

640

125 ... 160

800 ... 1600

--

--

--

800 ... 1600