3VT1 Molded Case Circuit Breakers up to 160 A

Circuit breakers · Switch disconnectors

2/11

Siemens LV 36 · 2008

2

Design

Installation and connection

Main circuit

• Is connected, using Cu or AI busbars, cables, and possibly

cables with cable lugs.

• For further connecting options, connecting sets can be used

(see page 2/9)

.

• Generally, conductors from the power supply are connected

to input terminals 1, 3, 5, (N) and conductors from the load to

terminals 2, 4, 6, (N). It is possible to reverse the current flow

inside the unit (i. e. infeed from below) without reducing the

rated short-circuit ultimate breaking capacity

I

cu

.

• In case of infeed from below, the units must be fitted with

3VT9 100-8CE30 phase barriers also on the side of terminals

2, 4, 6

(see pages 2/35 and 2/36)

.

• We recommend painting the connection busbars.

• Input and output connectors/busbars must be mechanically

reinforced to avoid transferring electrodynamic forces to the

circuit breaker during short-circuiting.

• The way of connecting the power circuit must observe the

deionization space of the circuit breaker/switch disconnector

(see pages 2/35 and 2/36)

.

Recommended cross-section of cables, busbars and flexibars

Auxiliary circuits

Switches, shunt trip releases or undervoltage releases are con-

nected directly to the terminals of the circuit breaker/switch dis-

connector using flexible Cu conductors with cross-section

0.5 ... 1 mm

2.

Conductor cross-sections of main terminals

Rated

current

I

n

Conductor cross-section S

Busbars W x H

Cu

AI

Cu

AI

A

mm

2

mm

2

mm

mm

16

2,5

--

--

--

20

2,5

--

--

--

25

4

--

--

--

32

6

--

--

--

40

10

--

--

--

50

10

16

--

--

63

16

25

--

--

80

25

35

--

--

100

35

50

16 x 2; 12 x 3 16 x 4; 12 x 4

125

50

95

16 x 4; 12 x 4 16 x 5; 12 x 6

160

70

120

16 x 5; 12 x 6 --

Order No.

Maximum

permitted

current

I

max

Maximum permissible conductor cross-sectionsS

Max. width of

busbars and

cable lugs

Technical

information

Cable type

Sector-shaped

conductor, stranded

Sector-shaped con-

ductor, solid

Round conductor,

stranded

Round conductor,

solid

A

mm

2

mm

2

mm

2

mm

2

mm

3-pole

3VT9 100-4TF30

160

2 x 25 ... 120

2 x 25 ... 120

2 x 25 ... 120

2 x 25 ... 120

pg. D17

3VT9 100-4TA30

160

16

3VT9 100-4RC30

160

16

pg. D18

3VT9 100-4TN30

10/16

1,5 ... 2,5/4 ... 6

--

--

3VT9 100-4ED30

160

30

pg. D18

4-pole

3VT9 100-4TF40

160

2 x 25 ... 120

2 x 25 ... 120

2 x 25 ... 120

2 x 25 ... 120

pg. 12

3VT9 100-4TA00

160

16

3VT9 100-4RC00

160

16

pg. 13

3VT9 100-4TN00

10/16

1,5 ... 2,5/4 ... 6