Page Background

3VT1 Molded Case Circuit Breakers up to 160 A

Circuit breakers · Switch disconnectors

2/12

Siemens LV 36 · 2008

2

Technical specifications

available,

-- unavailable,

+ in preparation

1)

When reversing the circuit breaker connection (power supply connected to

terminals 2, 4, 6, (N) output to terminals 1, 3, 5, (N)),

I

cu

does not change.

2)

Ranges of rated currents vary according to characteristics, see page 2/16.

3)

Permissible load of N pole is 100%.

Specifications

3VT1 7..-2..36-0AA0 3VT1 716-2DE36-0AA0 3VT1 7..-2..46-0AA0

3VT1 716-2EE46-0AA0

Order No.

Circuit Breakers Switch disconnectors Circuit Breakers

3)

Switch Disconnectors

Number of poles

3

4

Standards

EN 60 947-2,

IEC 947-2

EN 60 947-3,IEC 947-3 EN 60 947-2, IEC 947-2

EN 60 947-3,IEC 947-3

Approval marks

Rated current

I

n

A 16 ... 160

2)

--

16 ... 160

2)

--

Rated uninterrupted current

I

u

A 16 ... 160

2)

160

16 ... 160

2)

160

Rated operational current

I

e

A --

160

--

160

Rated operational voltage U

e

V max. AC 690

max. AC 690

max. AC 440

Rated frequency f

n

Hz 50/60

Rated impulse withstand voltage U

imp

kV 8

Rated insulation voltage U

i

V 690

Utilization category

• selectivity AC 690 V

A

--

A

--

• switching mode

AC-3 (16 ... 100 A)

AC-2 (100 ... 160 A)

AC-23 A

AC-3 (16 ... 100 A)

AC-2 (100 ... 160 A)

DC-22 A

AC-23 A

Rated short-time withstand current

I

cw

/t

--

2 kA/ 1 s

--

2 kA/1 s

Rated ultimate short-circuit breaking

capacity (rms value)

1)

I

cu

/U

e

6 kA/AC 690 V

12 kA/AC 500 V

25 kA/AC 415 V

40 kA/AC 230 V

--

13kA/DC 440V

(

τ =

max. 5 ms)

6 kA/AC 690 V

12 kA/AC 500 V

25 kA/AC 415 V

40 kA/AC 230 V

Off-time at

I

cu

ms 7

--

7

--

Rated service short-circuit breaking

capacity (rms value)

I

cs

/U

e

3 kA/AC 690 V

6 kA/AC 500 V

13 kA/AC 415 V

20 kA/AC 230 V

--

13kA/DC 440V

(

τ =

max. 5 ms)

3 kA/AC 690 V

6 kA/AC 500 V

13 kA/AC 415 V

20 kA/AC 230 V

Rated short-circuit making capacity

(peak value)

I

cm

/U

e

52 kA/AC 415 V 2.8 kA/AC 415 V

52 kA/AC 415 V

2.8 kA/AC 415 V

Losses per pole at

I

n

= 160 A

W see table, page 2/14 15

Mechanical endurance

cycles 20 000

Electrical endurance (U

e

= AC 415 V )

cycles 6 000

Frequency of switching

cycles/

hr

120

Operating force

N 55

65

Front-side device protection

IP40

Terminal protection

IP20

Operating conditions

Reference ambient temperature

°C 40

Ambient temperature range

°C -40 ... +55

Working environment

dry and tropical climate

Degree of pollution

3

Max. elevation

m 2000

Seismic resistance

Hz 3g (8 ... 50 )

Design modifications

Front/rear connection

/

Plug-in version

--

Withdrawable version

--

Accessories

Switches - auxiliary/relative/signal/leading

/–/

/–

Shunt trip/with signal switch

/

Undervoltage release/with leading

switch/with signal switch

/–/

Front hand drive/lateral drive right/left

/

/

Mechanical interlocking to the manual drive

by Bowden wire

--/--

–/

Motor. oper. mechanism/with oper. counter

+/+

+

Locking-type lever