3VT1 Molded Case Circuit Breakers up to 160 A

Accessories and Components

Auxiliary releases

2/24

Siemens LV 36 · 2008

2

Design

Auxiliary releases

Shunt release

Undervoltage release

Location of auxiliary releases

Auxiliary releases in compartment 10

Type designation according to the rated operational voltage

Type designation according to the rated operational voltage

The specific rated operational voltage of the shunt release is set

by jumpers directly on the release. The standard setting by the

manufacturer is always to the value corresponding to the type

designation.

Schematics

Shunt release

Undervoltage release

Technical specifications

U

e

Order No.

AC/DC 24/48 V

3VT9 100-1SC00

AC 110/230 V, DC 110/220 V

3VT9 100-1SD00

AC 230/400 V, DC 220 V

3VT9 100-1SE00

U

e

Order No.

AC/DC 24/48 V

3VT9 100-1UC00

AC 110/230 V /DC 110/220 V

3VT9 100-1UD00

AC 230/400 V /DC 220 V

3VT9 100-1UE00

B1

U

B2

10.Y2

N-

3VT9 100-1S.0

L+

NSO0_00055

10.Y1

A1

U

<

A2

10.Y2

N-

3VT9 100-1U.0

L+

NSO0_00056

10.Y1

Order No.

3VT9 100-1S.00

Rated operational voltage U

e

AC 24/48/110/230/400 V

DC 24/48/110/220 V

Rated frequency f

n

50/60 Hz

Input power at 1.1 U

e

• AC

2 VA

• DC

2 W

Characteristics

U

0.7 U

e

circuit breaker must trip

Time before switching off

15 ms

Loading time

Connection cross-section S

0,5 ... 1 mm

2

Terminal protection

(connected release)

IP20

Location in accessory compartment no. 10

SIGNAL SWITCH

- signals switching off by shunt trip

Rated operational voltage U

e

AC 230 V

Rated insulation voltage U

i

250 V

Rated impulse withstand voltage U

imp

4 kV

Rated frequency f

n

50/60 Hz

Rated operational current

I

e

/U

e

2 A/AC 230 V

Thermal current

I

th

6 A

Contact arrangement

01

Order No.

3VT9 100-1U.00

Rated operational voltage U

e

AC 24/48/110/230/400 V

DC 24/48/110/220 V

Rated frequency f

n

50/60 Hz

Input power at 1.1 U

e

• AC

2 VA

• DC

2 W

Characteristic

U

0.35 U

e

circuit breaker can be

switched on

U

0.85 U

e

circuit breaker must

trip

Time before switching off

15 ms

Loading time

Connector cross-section S

0.5 ... 1 mm

2

Terminal protection

(connected release)

IP20

Location in accessory compartment no. 10

SIGNAL SWITCH

- signals switching off of the undervoltage

Rated operational voltage U

e

AC 230 V

Rated insulation voltage U

i

250 V

Rated impulse withstand voltage U

imp

4 kV

Rated frequency f

n

50/60 Hz

Rated operational current

I

e

/U

e

2 A/AC 230 V

Thermal current

I

th

6 A

Contact arrangement

01