3VT5 Molded Case Circuit Breakers up to 1600 A

Circuit breakers · Switch disconnectors

6/12

Siemens LV 36 · 2008

6

Dimensional drawings

A, B, C - minimum deionization space, free of earthed metal

parts

Use of phase barriers and terminal covers with circuit breakers

and switch disconnectors.

Fixed-mounted design

Front connection

• terminals 1, 3, 5 (upper side)

3VT9 500-8CE30 phase barriers must always be installed on cir-

cuit breakers/switch disconnectors.

• Terminals 2, 4, 6 (bottom side)

- a) If circuit breakers/switch disconnectors are connected to

the supply using terminals 2, 4, 6, 3VT9 500-8CE30

phase barriers must always be installed on it.

- b) If circuit breakers/switch disconnectors are connected on

the bottom side using clamp or block type terminals,

3VT9 500-8CE30 phase barriers must always be installed on

it.

Rear connection

• terminals 1, 3, 5 (upper side)

3VT9 500-8CD30 insulating covers or 3VT9 500-8CE30

phase barriers must always be installed on the circuit

breaker/switch disconnector.

We recommend installing 3VT9 500-8CG30 insulating grommets

with all sets for rear connection.

• terminals 2, 4, 6 (bottom side)

If circuit breakers/switch disconnectors are connected to the

bottom side using clamp or block type terminals,

3VT9 500-8CD30 phase barriers must always be installed on it.

We recommend installing 3VT9 500-8CG30 insulating grommets

with all sets for rear connection.

Withdrawable version

Front connection

• terminals 1, 3, 5 (upper side)

If the withdrawable device is connected on the upper side using

clamp or block type terminals, 3VT9 500-8CF30 phase barriers

must always be installed.

In all other cases, we recommend installing 3VT9 500-8CC30

insulating covers on the upper side of the device.

• terminals 2, 4, 6 ( bottom side)

If the withdrawable device is connected to the bottom side using

clamp or block type terminals, 3VT9 500-8CF30 phase barriers

must always be installed.

In all other cases, we recommend installing 3VT9 500-8CC30

insulating covers on the bottom side of the withdrawable device.

NSO0_00522

OFF

ON

210

350

A = 100

50

B = 310

C = 134.5