Background Image
Table of Contents Table of Contents
Previous Page  210 / 267 Next Page
Information
Show Menu
Previous Page 210 / 267 Next Page
Page Background

3VT5 Molded Case Circuit Breakers up to 1600 A

Standard circuit breakers · Releases

6/8

Siemens LV 36 · 2008

6

Technical specifications

available,

-- unavailable,

+ in preparation

2) In case, the circiut breaker connection is reversed (input terminals 2, 4, 6

output terminals 1, 3, 5),

I

cu

does not change.

Specifications

3VT5 circuit breakers

Switch disconnectors

Type

Standards

EN 60 947-2, IEC 947-2

EN 60 947-3, IEC 947-3

Approval marks

Number of poles

3

Rated current

I

n

A

630, 1000, 1250, 1600

--

Rated normal current

I

u

A

1600

Rated operational current

I

e

A

--

1600

Rated operational voltage U

e

V

AC max. 690

AC max. 690

DC max. 440

Rated frequency f

n

Hz

50/60

Rated impulse withstand voltage U

imp

kV 8

Rated insulation voltage U

i

V

690

Utilization category (selectivity) AC 690 V

A, B

--

Utilization category (switching mode)

AC 690 V

DC 440 V

--

--

AC-23 B

DC-23 B

Rated short-time withstand current U

e

= AC 690 V

I

cw

/t

20 kA/1 s

Rated ultimate short-circuit breaking capacity

(rms value)

1)

I

cu

85 kA/AC 230 V

55 kA/AC 415 V

45 kA/AC 415 V

20 kA/AC 690 V

--

Off-time at

I

cu

ms

30

--

Rated short-circuit service breaking capacity (rms value)

I

cs

/U

e

45 kA/AC 230 V

36 kA/AC 415 V

30 kA/AC 500 V

20 kA/AC 690 V

--

Rated short-circuit making capacity

(peak value)

I

cm

/U

e

140 kA/AC 415 V

40 kA/AC 415 V

40 kA/AC 440 V

Losses per pole at

I

n

= 250 A

W 120

Mechanical endurance

cycles 10000

Electrical endurance (U

e

= AC 415 V )

4000

Switching frequency

cycles/

hr

120

Operating force

N 230

Front-side device protection

IP40

Terminal protection

IP20

Operating conditions

Reference ambient temperature

°C 40

Ambient temperature range

-40 ... +55

Working environment

dry and tropical climate

Degree of pollution

3

Max. elevation

m 2000

Seismic resistance

Hz

3g (8 ... 50)

Design modifications

Front/rear connection

/

Plug-in version

--

Withdrawable version

Accessories

Switches-auxiliary/relative/signal/leading

/

/--/--

Shunt release/with signal switch

Undervoltage release/with leading switch, with signal switch

/--

Front manual operating mechanism/lateral operating mechanism

right/left

/

Mechanical interlocking to the manual operating mechanism by

Bowden wire

/

Motorized operating mechanism/with operations counter

/

Locking-type lever

Bolt sealing insert/additional cover for overcurrent release

/--