3VT5 Molded Case Circuit Breakers up to 1600 A

Accessories and Components

Withdrawable version

6/14

Siemens LV 36 · 2008

6

Recommended wiring of circuit breaker, plug-in version

with motorized operating mechanism

Inserting and withdrawing circuit breaker with motorized

operating mechanism

• Each time before inserting or withdrawing the circuit breaker,

we recommend first to turn the AUTO/MANUAL switch on the

motor drive to the MANUAL position

• More information can be found in the operating

instructions

• Not adhering to this procedure or failing to follow the recom-

mended wiring could mean that the circuit breaker will not

successfully turn on at the first attempt

Changes in states of switches in cavities of switching unit when inserting and withdrawing circuit breaker

L+

Q3

X3

MP

NC NO

SSI

C

X3

5 7

6

3

2

4

9

6 2 1

1 10

5 7 3

3

4 1

M P

NSO0_00452

B

4.13

3VT9 500-2AF10

4.14

4.21

4.22

4.31

4.32

4.43

4.44

N-

Motor drive

ON

OFF

Switches

relative

acc.c. 4

Control circuit

Symbol

Description

MP

3VT9 500-3M..0 motorized operating mechanism

M

motor

P

storage device

X3

terminal strip to connect control circuits

X4

terminal strip for external operations counter

SSI

switch indicating AUTO (NO-C)/MANUAL (NC-C)

modes

B

recommended wiring of the control circuits (control cir-

cuits not included in motor driver delivery)

ON

make pushbutton

OFF

break pushbutton

Q3

Motorized operating mechanism circuit breaker for

AC 110 V LSN 4C/1

AC 230 V LSN 2C/1

DC 110 V LSN-DC 4C/1

DC 220 V LSN-DC 2C/1

State before insertion/withdrawal

State after insertion/withdrawal

Circuit breaker state before insertion

State of switches before insertion

-withdrawn position

State of switches after insertion

inserted position

Circuit breaker state before withdrawal

State of switches before withdrawal

inserted position

State of switches after withdrawal

withdrawn position

accessory compartment

accessory compartment

1,2

3,4

1,2

3,4

Lever position of

circuit breaker

State of the

main contacts

3VT9 500-2AF10

3VT9 500-2AF10

3VT9 500-2AF10

3VT9 500-2AF10

Switched on

1 1

0

0

1

1

0

1

0

Switched off manually or by motor drive

0 1

0

0

1

1

0

1

0

Switched off from the switched-on state: by

the release or TEST button

0 1

0

1

0

1

0

1

0

4

3

2

1

4

3

2

1

4

3

2

1

4

3

2

1