3VT5 Molded Case Circuit Breakers up to 1600 A

Circuit breakers · Switch disconnectors

6/10

Siemens LV 36 · 2008

6

Functions

Switching states in the circuit breaker cavities

0 = contact open

1 = contact closed

Design

Main circuit

• Connected with Cu/Al busbars or cables, and possibly cables

with cable lugs.

• For greater connecting options, connecting sets are produced

(see page 6/6).

• Generally, conductors from the power supply are connected

to input terminals 1, 3, 5, (N) and conductors from the load to

terminals 2, 4, 6, (N). However, it is possible to reverse this

connection (switching of input and output terminals) without

limiting rated short-circuit ultimate breaking capacity

I

cu

.

• In case of reversed connection, the circuit breaker/switch dis-

connector must be provided with 3VT9 500-8CE30 phase

barriers also on the side of terminals 2, 4, 6 (for detailed infor-

mation, see page 6/12).

• We recommend painting the connecting busbars.

• Input and output conductors/busbars must be mechanically

reinforced to avoid transmitting electrodynamic force to the

circuit breaker/switch disconnector during short-circuiting.

• The way of connecting the main circuit must observe the

circuit breaker’s deionization spaces (see page 6/12).

Auxiliary circuits

• Switches, shunt releases or undervoltage releases are con-

nected using flexible 0.5 ... 1 mm

2

Cu conductors to the

terminals on these devices.

• Auxiliary circuits of the withdrawable version are connected

using a connector.

Recommended cross-sections for cables, busbars and flexibars

for fixed-mounted, plug-in and withdrawable versions

1)

The withdrawable device connected by 2 x 50 x 12 mm Cu busbars can be

loaded with max. 1420 A. For 1600 A loading, the withdrawable version

must be connected by 2 x 50 x 12 mm busbars.

Maximum circuit breaker/switch disconnector loads in

accordance with ambient temperature

3VT4 circuit breaker/switch disconnector - connection of

Cu busbars 2 x 50 x 6 mm to pole

3VT5 circuit breaker/switch disconnector - connection of

Cu busbars 2 x 50 x 6 mm to pole

3VT5 circuit breaker/switch disconnector - connection of

Cu busbars 2 x 50 x 10 mm to pole

Accessory compartment

1, 2

3, 4

Cicuit breaker position

Lever positon

of circuit breaker

State of the main contacts

3VT9 500-2AF10

3VT9 500-2AF10

Switched on

1

1 0 0 1 1 0 0 1

Switched off manually or

electrically by operating

mechanism

0

0 1 1 0 1 0 0 1

Switched off by the overcurrent

release, auxiliary release or by

TEST pushbutton

0

0 1 1 0 0 1 1 0

Rated current

I

n

Permissible cross-

section S

Busbars W x H

Cu

AI

Cu

Al

A

mm

2

mm

2

mm

mm

250

120

150

400

185

240

500

2 x 150 2 x 185

630

2 x 185 2 x 240

800

2 x 240 3 x 240 50 x 10 2 x 50 x 5 2 x 50 x 8

1000

2 x 240 3 x 240 2 x 50 x 6

1300

3 x 240 4 x 240

2 x 50 x 10

1500 (1450)

1)

4 x 240

2 x 50 x 10

1600 (1450)

1)

2 x 50 x 10

1)

50 °C

55 °C 60 °C

65 °C

70 °C

1000 A

1000 A 1000 A

1000 A

980 A

50 °C

55 °C 60 °C

65 °C

70 °C

1400 A

1400 A 1340 A

1260 A

1200 A

50 °C

55 °C 60 °C

65 °C

70 °C

1600 A

1540 A 1460 A

1400 A

1320 A