www.furse.comESP MC Series
TSC-0912 - 09.10.12
Technical specification
Electrical specification - mains
ESP MC
ESP MC/TN/RJ11
ESP MC/Cat-5e
Nominal voltage - Phase-Neutral
U
o
(RMS)
220/230/240 V
Maximum voltage - Phase-Neutral
U
c
(RMS)
280 V
Frequency range
47-63 Hz
Current rating
(supply)
13 A
Leakage current
(to earth)
< 0.5 mA
Electrical specification - telecom/data
Nominal voltage
-
296 V
5 V
Maximum working voltage
U
c
1
-
296 V
5 V
2
Current rating
(signal)
-
300 mA
300 mA
In-line resistance
(per line ±10%)
-
4.4
Ω
1
Ω
Bandwidth
(-3 dB 50
Ω
system)
-
20 MHz
-
Maximum data rate
-
-
100 Mbps
Transient specification - mains
ESP MC
ESP MC/TN/RJ11
ESP MC/Cat-5e
Type 2 (BS EN/EN), Class II (IEC)
Nominal discharge current 8/20 µs (per mode)
I
n
5 kA
Let-through voltage
U
p at
I
n
3
850V
Maximum discharge current
I
max (per mode)
4
10 kA
Type 3 (BS EN/EN), Class III (IEC)
Let-through voltage at
U
oc of 6 kV 1.2/50 and
I
sc of
3 kA 8/20 (per mode)
5
680 V
Let-through voltage at
U
oc of 6 kV 1.2/50 and
I
sc of
500 A 8/20 (per mode)
555 V
Transient specification - telecom/data
Let-through voltage
(all conductors)
6
U
p
C2 test 4 kV 1.2/50 µs, 2 kA 8/20 µs to
BS EN/EN/IEC 61643-21 - line to line / line to earth
-
390 V/390 V
120 V/700 V
8
C1 test 1 kV, 1.2/50 µs, 0.5 kA 8/20 µs to
BS EN/EN/IEC 61643-21 - line to line / line to earth
-
395 V/395 V
74 V/600 V
8
B2 test 4 kV 10/700 µs to BS EN/EN/IEC 61643-21
- line to line / line to earth
-
295 V/295 V
21 V/550 V
8
5 kV, 10/700 µs
7
- line to line / line to earth
-
300 V/300 V
25 V/600 V
8
Maximum surge current
9
D1 test 10/350 µs to BS EN/EN/IEC 61643-21
-
1 kA
1 kA
8/20 µs to ITU (formerly CCITT), BS 6651:1999 Appendix C
-
10 kA
10 kA
Mechnical specification
ESP MC
ESP MC/TN/RJ11
ESP MC/Cat-5e
Temperature range
-25 °C to +80 ºC
Connection type
Via British style three square pin plug and socket to BS 1363
Connection type - telecom/data
-
RJ11
RJ45
Earth connection
Via plug and socket
Case material
Steel
Weight -
unit
1.70 kg
1.75 kg
1.75 kg
Weight
-
packaged
1.75 kg
1.8 kg
1.8 kg
1
Maximum working voltage (DC or AC peak) of telecom/data protection measured at <10 µA leakage for ESP MC/TN/RJ11 and 1 mA for ESP MC/Cat-5e.
2
Maximum working voltage is 5 V for data pairs 1/2 & 3/6.
3
The maximum transient voltage let-through of the protector throughout the test (±5%), phase to neutral, phase to earth and neutral to earth.
4
The electrical system, external to the unit, may constrain the actual current rating achieved in a particular installation.
5
Combination wave test within BS EN/IEC 61643, IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010, AS/NZS 1768-2007, UL 1449 mains wire-in.
6
The maximum transient voltage let-through the protector throughout the test (±10%), line to line & line to earth. Response time < 10 ns.
7
Test to BS EN/IEC 61643, IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20, K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002, ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68).
8
The interfaces used in Cat-5/5e systems incorporate an isolation transformer that inherently provides an inbuilt immunity to transients between line and earth of 1,500 Volts or more.
9
The installation and connectors external to the protector may limit the capability of the protector.