Technical

information

Lighting

Ingress protection system

EN 60529

The resistive performance of fittings to solids and liquids is indicated by the IP (Ingress Protection) prefix followed by two numbers. The first

number indicates the measure of protection against the ingress of solids.

The second number indicates the measure of protection against the ingress of liquids.

Protection against the ingress of solids

First identification number

Number

Measure of protection

Test

IP2X

Against foreign bodies > 12mm Ø

Ball 12mm Ø and finger test

IP3X

Against foreign bodies > 2.5mm Ø

Steel wire 2.5mm Ø

IP4X

Against foreign bodies > 1.0mm Ø

Steel wire 1.0mm Ø

IP5X

Against harmful dust deposits (dust proof)

Talcum powder – particles 1 μm Ø

IP6X

Against any entry of dust (dust light)

Talcum powder – particles 1 μm Ø

Protection against the ingress of liquids

Second identification number

Number

Measure of protection

Test

IPX1

Against falling drops of water

Water falling vertically

IPX2

Against falling drops of water

Water falling up to 15º from vertical

IPX3

Against falling drops of water (rain proof)

Water falling up to 60º from vertical

IPX4

Against splashed water (splash proof)

Water from all directions

IPX5

Against jets of water (jet proof)

Water from all directions projected by a nozzle

IPX6

Against heavy seas or powerful water jets

Water from all directions projected by a nozzle

IPX7

Against prolonged immersion effects, but not for

continuous underwater application

Immersion in water > 1m for 30 minutes

IPX8

Against prolonged submersion

Immersion in water > 1m max for 30 minutes –

max. depth tested indicated after symbol (pressure

water-tight)

These illustrations and the advice opposite are based

on BS 7671:2008 the IEE Wiring Regulations 17th

Edition, Section 701. For full details please look in

this document. For lighting installed in Zone 1 and 2

all luminaires must be at least IPX4, or IPX5 if water

jets are used for cleaning. All circuits for current-using

equipment and accessories must be protected by

RCD’s of 30mA rating. SELV (12V ac) luminaires must

have the SELV source (transformer) outside the zones

e.g. in the ceiling void.

Current-using equipment and accessories in locations containing a bath or

shower