Thermal characteristics of

switchboards

Two cubicles with busbar compartment, 800 mm

wide, 400 mm deep, IP30

Diversity factor: 0.7 and 0.8

Ambient temperature around the switchboard: 35 °C

Cubicle

1

: P(W) of device zone = 580 W

Cubicle

2

: P(W) of device zone = 180 W

NSX250

NSX NSX NSX NSX

NSX400

LGY

Linergy FM

Linergy FC distribution block

DD400000.eps

Two cubicles with busbar compartment, 800 mm

wide, 1000 mm deep, two 300 mm wide ducts, IP30

Diversity factor: 0.7

Ambient temperature around the switchboard: 35 °C

Cubicle

1

: P(W) of device zone = 880 W

Cubicle

2

: P(W) of device zone = 330 W

NSX400

NSX NSX NSX NSX

NSX630

Linergy LGY