Additional information

Thermal characteristics of

switchboards

Calculation of the internal

temperature

Calculation of the temperature is the means to check that the enclosure can

evacuate the dissipated power of the installed devices.

Important note

Correct thermal management of the switchboard depends on compliance with

the installation requirements for the distribution system (power circuits).

Incorrect installation will have major consequences on the connected device, but

almost none on the internal temperature of the enclosure.

Once the circuit has been correctly sized, it is necessary to check whether the

assembly (devices + distribution system + cables) have a level of dissipated power

P(W)

y

the P(W) that the enclosure can handle.

Dd381401.eps

Method defined by IEC 890 technical report

This IEC guide for switchboards proposes a calculation method to determine three

levels of internal temperature, depending on the dissipated power of the devices and

distribution blocks installed in the switchboard.

Users can consult this document when it is necessary to determine precisely the

internal temperature in view of optimising the switchboard.

On request, Schneider Electric can carry out a thermal study to check that the

installed assembly and the thermal capacity of the enclosure are compatible.

DD381350.eps

Comparative method

A number of qualified and tested configurations serve as the basis for indicating the

thermal capacity of Prisma P enclosures.

This is en empirical means to check whether the dissipated power of the desired

configuration is close to that of a tested configuration.

DD382422.eps

Method using charts taking into account enclosure characteristics

To speed up calculations, Schneider Electric produces charts based on the

company’s experience and a number of assumptions on the installation.

They can be used sufficiently precisely to determine the variations in temperature

and the dissipated-power levels for the different types of wall-mounted enclosures,

floor-standing enclosures and cubicles.

For details on the calculation of the dissipated power in the device zone, see page

D-80.

Thermal management

of switchboards

General