Page Background

Fan

Grill with filter

PB501053_35.eps

PB501046_35.eps

Catalogue numbers

NSYCVF560M230PF

NSYCVF850M230PF

NSYCAG291LPF

Power rating (W)

68/85

150/195

-

Noise level (dB)

59/59

76/75

-

Unimpeded

throughput

50 Hz 562 m

3

838 m

3

-

60 Hz 586 m

3

803 m

3

-

Throughput with

counterpressure

(grill + standard filter)

50 Hz 473 m

3

718 m

3

-

60 Hz 477 m

3

568 m

3

Weight (kg)

3.2

4.1

-

Installation

Generally installed at the bottom of floor-standing enclosures:

b

b

by cutting out a side panel,

b

b

or by using the front plate with cut-out for fan or grill, directly clipped on (03890).

Characteristics

The set comprises the fan with a grill and a filter.

b

b

Input voltage: 230 V (50/60 Hz).

b

b

Degree of protection: IP54.

b

b

RAL 7035.

b

b

Material: ABS

Supplied with standard filter.

b

b

Maximum throughput 350 m

3

/h.

b

b

Degree of protection: IP54.

b

b

RAL 7035.

b

b

Material: ABS.

Dimensions

316

336

DB300474.eps

B

A

9.5

290.7

18

DB300475EN.eps

291

x

291

DB300476.eps

9.5

18

DD385319.eps

Functional system

Accessories

Management of the internal

temperature

Filters for grill

Standard filters

Fine filters

Catalogue numbers

NSYCAF291

NSYCAF291T

Characteristics

Set of 5 (for replacement)

G2 M1 synthetic filter

Set of 5 (for replacement)

G3 M1 synthetic filter

Front plate L = 600 For fan and grill

Ventilated front plate

DD60759.eps

Dd381676.eps

Catalogue number

03890

03891

03895

Height

7 modules

H = 350 mm

1 vertical module,

H = 50 mm

3 vertical modules,

H = 150 mm

Characteristics

Front plate with cut-out.

Degree of protection: IP30.

Degree of protection: IP30.

Located at the top and bottom of the switchboard, IP30 ventilated front plates facilitate

natural convection in the switchboard.

Surface area of the openings -

80 cm

2

250 cm

2

Ventilation

In most cases and notably for IP30 switchboards, the heat dissipation by convection

takes place naturally and does not require fans.

However, when the switchboard is installed in temperate environments or when the

degree of protection is high (IP54), ventilation accessories are indispensable.

For more in-depth information on selecting air-conditioning accessories and the thermal

management of switchboards

> page 199 to page 206

.

A

B

Catalogue number

225

160.5 NSYCVF560M230PF

280

192

NSYCVF850M230PF

77