Presentation
Enclosures
PrismaGenclosures
Prisma G W600, W300
IP30, IP31, IP43
Metallic indoor enclosures to compose.
Commercial buildings: hotels, offices, shops, etc.
Industry: technical room, etc.
Main characteristics
Steel sheet metal with electrophoresis treatment + hot-polymerised polyester
epoxy powder.
Enclosure:
b
b
width: 595 mm, with duct: 305 mm
b
b
height: 330 to 1380 mm
b
b
depth: 205 mm without door / 250 mm with door
b
b
properties of metal enclosures
> page 198
.
Designation
G IP30 - IP31 - IP43 enclosure
Rated operational current
630 A
- Isc = 50 kA, Icw = 25 kA rms / 1 s, Ipk = 53 kÂ
Colour
White colour RAL 9001
Standards conformity
EN 62208, IEC 61439-2
Degree of protection
IP30 with or without door,
IP31 with canopy + door,
IP43 with canopy + door + gasket
Degree of protection against
mechanical impacts
IK08 with door,
IK07 without door
Isolation
Class 1
Doors
b
b
Plain or transparent, opening to right or left
b
b
By design, electrical continuity of moving parts (hinges…)
b
b
Supplied with a handle and keylock (key 405)
Distance behind door = 58 mm (possibility of push-buttons,
lamps installation).
Mounting
Surface mounting, floor-standing, flush mounting via a kit
> page 117
b
b
630 A
b
b
IP30
b
b
IK07/08
Enclosuredeliveredflat: total accessibility
Designedfor electrical continuity
Continuity of service
b
b
Direct accessibility of functional
unit thanks to the front plate
hinges kit
b
b
Total accessibility of switchgear
thanks to the installation of hinges
on all front plate (allows the front
panel to be made swivelling)
Easy designwith
Rapsody
software
> seepage 27
PD390240_SE-48.eps
PD390300_SE-11_2013.eps
Fast operation and
easy maintenance
b
b
Straightforward
organisation in
functional units
Safety
b
b
Insulated Linergy BW
busbars, IPxxB, pre-fitted
Quick-connect
Linergy TB terminal
blocks
Gland plate
b
b
Dismountable
and cuttable
Ergonomic handle
Quick fastening
on hook-on rail
b
b
Easy wall mounting
Ergonomics and safety
b
b
Easy front plate handling
thanks to the ergonomic
gripper
b
b
Legible "Open/closed"
positions of front plate
b
b
Integrated front plate
sealing function
113