D-35

Electrical diagrams

Electrical interlocking with lockout after a fault

DB401827

ATTENTION

(1)

Not to be wired for the “without lockout after a fault” solution.

(2)

Not to be wired on fixed version.

(3)

Prefabricated wiring supplied.

The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with

switch-disconnectors, connect

wire BK to terminal 82.

Legends

QN

“Normal” source Masterpact NT or NW

QR

“Replacement” source Masterpact NT or NW

MCH

spring-charging motor

MX

standard opening voltage release

XF

standard closing voltage release

OF...

breaker ON/OFF indication contact

SDE1

“fault-trip” indication contact

PF

“ready-to-close” contact

CE1

“connected-position” indication contact (carriage switch)

CH

“springs charged” indication contact

IVE

electrical interlocking and terminal block unit

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Wiring colour codes

Note:

diagram shown with circuit breakers in connected position, open,

charged, and ready to close.

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Source-changeover systems

with automatic controllers

2 Masterpact NT or NW devices

Diagram no. 51156903