Electrical diagrams

2 sources and 1 coupling: automatic-control system with lockout after a fault

DB101749

ATTENTION

The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with

switch-disconnectors, connect

the SDE to terminals 81 and 84.

Legends

QS...

“Source” Masterpact NW

QC

“Coupling” Masterpact NW

MCH

spring-charging motor

MX

standard opening voltage release

XF

standard closing voltage release

OF...

breaker ON/OFF indication contact

SDE1

“fault trip” indication contact

PF

“ready-to-close” contact

CE..

. “connected-position” indication contact (carriage switch)

CH

“springs charged” indication contact

F1

auxiliary power supply circuit breaker

F2/F3

circuit breaker (high breaking capacity)

S1

control switches

S2

source selection switches

KA1

auxiliary relays with 10 to 180 sec. time delay

KA2

auxiliary relays with 0.1 to 30 sec. time delay

KA3

auxiliary relays with 10 to 180 sec. time delay

KA4

auxiliary relays with 0.1 to 30 sec. time delay

KA5

auxiliary relays with 0.25 sec. time delay

KA6

auxiliary relays with 0.25 sec. time delay

KA7

auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system

and with associated automatism

Source 1 Source 2 Coupling

0

0

0

1

1

0

1

0

1

0

1

1

1

0

0

0

1

0

0

0

1

Note:

diagram shown with circuit breakers in connected position, open,

charged, and ready to close.

Auxiliary power supply = supply voltage of auxiliary relays (KA...)

= supply voltage of electrical auxiliaries (electrical operation,

MCH, MX, MN...).

Remote-operated

source-changeover systems

3 Masterpact NW devices

Diagram no. 51156914