Table of Contents Table of Contents
Previous Page  16 / 182 Next Page
Information
Show Menu
Previous Page 16 / 182 Next Page
Page Background

A-2

Functions

and characteristics

Masterpact NT06 to NT16 installation characteristics

Circuit breaker

NT06, NT08, NT10

NT12, NT16

Type

H1

H2

L1

H1

H2

Connection

Drawout

FC

b

b

b

b

b

RC

b

b

b

b

b

Fixed

FC

b

b

b

b

b

RC

b

b

b

b

b

Dimensions (mm) H x W x D

Drawout

3P

322 x 288 x 277

4P

322 x 358 x 277

Fixed

3P

301 x 276 x 196

4P

301 x 346 x 196

Weight (kg) (approximate)

Drawout

3P/4P

30/39

Fixed

3P/4P

14/18

Masterpact NW08 to NW63 installation characteristics

Circuit breaker

NW08, NW10, NW12, NW16

NW20

Type

N1

H1

H2

L1

H10

H1

H2

H3

L1

H10

Connection

Drawout

FC

b

b

b

b

-

b

b

b

b

-

RC

b

b

b

b

b

b

b

b

b

b

Fixed

FC

b

b

b

-

-

b

b

-

-

-

RC

b

b

b

-

-

b

b

-

-

-

Dimensions (mm) H x W x D

Drawout

3P

439 x 441 x 395

4P

439 x 556 x 395

Fixed

3P

352 x 422 x 297

4P

352 x 537 x 297

Weight (kg) (approximate)

Drawout

3P/4P

90/120

Fixed

3P/4P

60/80

(1)

Except 4000

Circuit breakers

and switch-disconnectors

NT06 to NT16 and NW08 to NW63

NT and NW selection criteria

Masterpact NT

Masterpact NW

Standard applications

Standard applications

NT06, NT08, NT10, NT12, NT16

NT06, NT08, NT10

NW08...NW16

NW08...NW40

H1

H2

L1

N1

H1

Type of application

Standard applications

with low short-circuit

currents

Applications with

medium-level short-

circuit currents

Limiting circuit breaker

for protection of cable-

type feeders or

upgraded transformer

ratings

Standard applications

with low short-circuit

currents

Circuit breaker for

industrial sites with

high short-circuit

currents

Icu/Ics at 440 V

42 kA

50 kA

130 kA

42 kA

65 kA

Icu/Ics at 1000 V

-

-

-

-

-

Icu/Ics at 500 V DC L/R < 15 ms

-

-

-

-

-

Position of neutral

Left

Left

Left

Left

Left or right

Fixed

F

F

F

F

F

Drawout

D

D

D

D

D

Switch-disconnector version

Yes

No

No

Yes

Yes

Front connection

Yes

Yes

Yes

Yes

Yes up to 3200 A

Rear connection

Yes

Yes

Yes

Yes

Yes

Type of Micrologic control unit

A, E, P, H

A, E, P, H

A, E, P, H

A, E, P, H

A, E, P, H

version: 8.2

207E2100.indd