A-8

All Masterpact circuit breakers are equipped with a

Micrologic control unit that can be changed on site.

Control units are designed to protect Power circuits

and loads. Alarms may be programmed for remote

indications.

Measurements of current, voltage, frequency, power

and power quality optimise continuity of service and

energy management.

Dependability

Integration of protection functions in an ASIC electronic component used in all

Micrologic control units guarantees a high degree of reliability and immunity to

conducted or radiated disturbances.

On Micrologic A, E, P and H control units, advanced functions are managed by an

independent microprocessor.

Accessories

Certain functions require the addition of Micrologic control unit accessories,

described on

page A-25

.

The rules governing the various possible combinations can be found in the

documentation accessible via the Products and services menu of the

www.schneider-electric.com

web site.

Micrologic name codes

Current protection

X: type of protection

2 for basic protection

b

b

5 for selective protection

b

b

6 for selective + earth-fault protection

b

b

7 for selective + earth-leakage protection.

b

b

Y: control-unit generation

Identification of the control-unit generation.

“0” signifies the first generation.

Z: type of measurement

A for “ammeter”

b

b

E for “energy”

b

b

P for “power meter”

b

b

H for “harmonic meter”.

b

b

Micrologic 2: basic protection

DB101116

Protection:

long time

+ instantaneous

Micrologic 5: selective protection

DB101117

Protection:

long time

+ short time

+ instantaneous

Micrologic 6: selective + earth-fault protection

DB101117

DB101118

Protection:

long time

+ short time

+ instantaneous

+ earth fault

Micrologic 7: selective + earth-leakage protection

DB101117

DB101119

Protection:

long time

+ short time

+ instantaneous

+ earth leakage up to 3200A