5

Positive contact indication

All Compact NS circuit breakers are suitable for isolation as defined in IEC standard

60947-2:

the isolation position corresponds to the O (OFF) position

b

the operating handle cannot indicate the “OFF” position unless the contacts are

b

effectively open

padlocks may not be installed unless the contacts are open.

b

Installation of a rotary handle or a motor mechanism does not alter the reliability

of the position-indication system.

The isolation function is certified by tests guaranteeing:

the mechanical reliability of the position indication system

b

the absence of leakage currents

b

overvoltage withstand capacity between upstream and downstream connections.

b

Installation in class II switchboards

All Compact NS circuit breakers are class II front face devices. They may be installed

through the door of class II switchboards (as per IEC standard 60664), without

downgrading switchboard insulation. Installation requires no special operations,

even when the circuit breaker is equipped with a rotary handle or a motor

mechanism.

Degree of protection

As per standards IEC 60529 (IP degree of protection) and EN 50102

(IK degree of protection against external mechanical impacts).

Bare circuit breaker with terminal shields

With toggle

IP40 IK07

With direct rotary handle

IP40 IK07

standard / VDE

Circuit breaker installed in a switchboard

With toggle

IP40 IK07

With direct rotary handle

standard / VDE

MCC

CNOMO

IP40 IK07

IP435

IP547

With extended rotary handle

IP55 IK08

DB128019

DB128018

DB128017

DB128016

DB128015

DB401831