Background Image
Table of Contents Table of Contents
Previous Page  14 / 148 Next Page
Information
Show Menu
Previous Page 14 / 148 Next Page
Page Background

4

Compliance with standards

Compact NS circuit breakers and auxiliaries comply with the following:

international recommendations:

b

IEC 60947-1 - general rules

v

IEC 60947-2 - circuit breakers

v

IEC 60947-3 - switches, disconnectors, switch-disconnectors, etc.

v

IEC 60947-4 - contactors and motor starters

v

IEC 60947-5.1 and following - control circuit devices and switching elements;

v

automatic control components

European (EN 60947-1 and EN 60947-2) and the corresponding national

b

standards:

France NF

v

Germany VDE

v

U.K. BS

v

Australia AS

v

Italy CEI

v

the specifications of the marine classification companies (Veritas, Lloyd’s Register

b

of Shipping, Det Norske Veritas, etc.)

French standard NF C 79-130 and the recommendations issued by the CNOMO

b

organisation for the protection of machine tools.

For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please

consult us.

Pollution degree

Compact NS circuit breakers are certified for operation in pollution-degree 3

environments as defined by IEC standard 60947 (industrial environments).

Tropicalisation

Compact NS circuit breakers have successfully passed the tests prescribed by the

following standards for extreme atmospheric conditions:

IEC 60068-2-1 - dry cold (-55 °C)

b

IEC 60068-2-2 - dry heat (+85 °C)

b

IEC 60068-2-30 - damp heat (95 % relative humidity at 55 °C)

b

IEC 60068-2-52 - salt mist (severity level 2).

b

Environmental protection

Compact NS circuit breakers take into account important concerns for environmental

protection. Most components are recyclable and the parts of Compact NS630b to

NS3200 circuit breakers are marked as specified in applicable standards.

Ambient temperature

Compact NS circuit breakers may be used between -25 °C and +70 °C.

b

For temperatures higher than 40 °C (65 °C for circuit breakers used to protect motor

feeders), devices must be derated as indicated in the documentation.

circuit-breakers should be put into service under normal ambient operating-

b

temperature conditions. Exceptionally, the circuit breaker may be put into service

when the ambient temperature is between -35 °C and -25 °C.

the permissible storage-temperature range for Compact NS circuit breakers in the

original packing is -50 °C

(1)

to +85 °C.

Discrimination

As standard, the Compact NS range ensures discrimination between two circuit

breakers positioned in series in an installation.

Introduction

General characteristics

for NS630b to 3200 range

(1)

-40 °C for Micrologic control units with an LCD screen.

Standardised characteristics indicated on the rating plate:

Ui:

rated insulation voltage

Uimp:

rated impulse withstand voltage

Icu:

ultimate breaking capacity, for various values

of the rated operational voltage Ue

cat:

utilisation category

Icw:

rated short-time withstand current

Ics:

service breaking capacity

In:

rated current

suitable for isolation

DB401560

IEC 60947-2

UTE VDE

BS CEI

UNE AS

NEMA

Ui

800 V

Uimp

8 kV

Icw

19.2kA / 1s

cat B

NS630b H

Ue

(V)

Compact

Icu

(kA)

Ics

(kA)

220/240

a

70 35

380/415

a

70 35

440

a

65 32

500/525

a

50 25

660/690

a

42 21

50/60Hz

DB128013

CB2

CB1

Presentation