3

Protection

of LV

distribution

systems

page A-2

Protection

of

motors feeders

(AC 220/690 V)

page A-35

Control and

isolation

using

switch-

disconnectors

page A-37

Service

connection

Source

changeover

systems

page A-44

Protection for:

distribution systems supplied by transformers

b

distribution systems supplied by engine

b

generator sets

long cables in IT and TN systems.

b

Installation :

in power switchboards.

b

All circuit breakers in the Compact NS range offer

positive contact indication

and are suitable for isolation in compliance with

standards IEC 60947-1 and 2.

When combined with a motor starter, Compact NS

circuit breakers protect the cables and the starter

against short-circuits.

Equipped with an electronic trip unit, Compact NS

circuit breakers also protect the cables, starter and

motor against overloads.

The exceptional current-limiting capacity of

Compact NS circuit breakers automatically

ensures type-2 coordination with the motor starter,

in compliance with standard IEC 60947-4-1.

Compact NS service connection circuit breakers are

specially designed for the service-connection function:

lead seals and locking systems

b

tripping curves certified by utilities

b

fast overload curves to limit the power supplied, etc.

b

Interpact INV switch-disconnectors offering visible

break (see the corresponding catalogue) can be

combined with Compact NS circuit breakers to

constitute the various types of service connections

and meet the needs of all installation configurations.

A switch-disconnector version of Compact NS circuit

breakers exists for circuit control and isolation.

All the additional functions may be combined with the

basic switch-disconnector function, including:

earth-leakage protection

b

motor mechanism.

b

For information on other switch-disconnector ranges,

see the Interpact (offering positive contact indication

and visible break) and Fupact (fuse switch) catalogues.

To ensure a continuous supply of power, some

electrical installations are connected to two power

sources:

a normal source

b

a replacement source to supply the installation

b

when the normal source is not available.

Amechanical and/or electrical interlocking system

between two circuit breakers or switch-disconnectors

avoids all risk of parallel connection of the sources

during switching.

A source-changeover system can be:

manual with mechanical device interlocking

b

remote controlled with mechanical and/or electrical

b

device interlocking

automatic by adding a controller to manage

b

switching from one source to the other on

the basis of external parameters.

(See Source-changeover catalogue for dimensions,

connections and electrical drawings).

Additional earth-leakage protection protects life

and property against the risks of faulty insulation

in the installation.

Depending on the circuit breaker,

earth-leakage protection is provided by:

using a specific Micrologic control unit

b

using a Vigirex relay and separate toroids.

b

Earth

leakage

page A-36