Earth-leakage protection

Connection of the rectangular-sensor secondary

circuit

Compact equipped with a Micrologic 7 A/P:

use the cable shipped with the rectangular sensor.

DB128388

Micrologic 7

4Z

3Z

2Z

1Z

5Z

I

Q

M1

M2

M3

U

M1

M2

T3

F2+

T2

T1/M3

T4/F1

L2 L3

L1 N

Neutral protection

three pole circuit breaker:

b

neutral protection is impossible with Micrologic A

v

with Micrologic E, P, an external neutral transformer

v

is necessary; the connection diagram is the same as

for residual earth-fault protection.

four pole circuit breaker:

b

Compact equipped with Micrologic A

v

the current transformer for external neutral is not

v

necessary.

Zone selective interlocking

Zone-selective interlocking is used to reduce the

electrodynamic forces exerted on the installation by shortening

the time required to clear faults, while maintaining time

discrimination between the various devices.

A pilot wire interconnects a number of circuit breakers

equipped with Micrologic A/E/P control units, as illustrated in

the diagram above.

The control unit detecting a fault sends a signal upstream and

checks for a signal arriving from downstream. If there is a

signal from downstream, the circuit breaker remains closed for

the full duration of its tripping delay. If there is no signal from

downstream, the circuit breaker opens immediately, regardless

of the tripping-delay setting.

Fault 1.

Only circuit breaker A detects the fault. Because it receives no

signal from downstream, it immediately opens in spite of its

tripping delay set to 0.3.

Fault 2.

Circuit breakers A and B detect the fault. Circuit breaker A

receives a signal from B and remains closed for the full duration

of its tripping delay set to 0.3. Circuit breaker B does not receive

a signal from downstream and opens immediately, in spite of its

tripping delay set to 0.2.

Wiring

Maximum impedance: 2.7

b

Ω

/ 300 m.

Capacity of connectors: 0.4 to 2.5 mm

b

2.

Wires: single or multicore.

b

Maximum lenght: 3000 m.

b

Limits to device interconnection:

b

the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2)

v

can be connected to a maximum of 10 upstream device

a maximum of 100 downstream devices may be connected

v

to the common ZSI - IN (Z3) and to an input ZSI - IN CR ( Z4) or

GF (Z5).

Downstream

circuit break

Fault 1

Fault 2

Upstream

circuit break

tsd = 0.3

tsd = 0.2

A

B

Compact NS630b to 3200

Earth-fault and earth-leakage protection

Neutral protection

Zone selective interlocking