D-8

Compact NS630b to 3200

Earth-fault and earth-leakage protection

Neutral protection

Zone selective interlocking

Electrical diagrams

External sensor (CT) for residual earth-fault protection

Connection of current-transformer secondary

circuit for external neutral

Compact equipped with a Micrologic 6 A/E/P:

(1)

shielded cable with 2 twisted pairs

b

T1 twisted with T2

b

maximum length 4 meters

b

cable cross-sectional area 0.4 to 1.5 mm

b

2

recommended cable: Belden 9552 or equivalent.

b

For proper wiring of neutral CT, refer to instruction

Bulletin 48041-082-03 shipped with it.

Do not remove Micrologic factory-installed jumper

between T1 and T2 unless neutral CT is connected.

If supply is via the top, follow the shematics.

If supply is via the bottom, control wiring is identical; for

the power wiring, H1 is connected to the source side,

H2 to the load side.

For four-pole versions, for residual earth-fault

protection, the current transformer for the external

neutral is not necessary.

Connection for signal VN is required only for power

measurements (3 Ø, 4 wires, 4CTs).

(1)

Only for NS630b to 1600.

DB125601

Shield Drain

External transformer for source ground return (SGR) earth-fault protection

Connection of the secondary circuit

Compact equipped with a Micrologic 6 A, E, P

(1)

:

unshielded cable with 1 twisted pair

b

maximum length 150 metres

b

cable cross-sectional area 0.4 to 1.5 mm

b

2

recommended cable: Belden 9409 or equivalent.

b

(1)

Only for NS630b to 1600.

DB128387

Q

Micrologic 6

PE

X1

X2

8

14

11 10

12 5 6 7

13

9

3

1

H1

H2

MiDGF module

M1

M2

T3

F2+

T2

T1/M3

T4/F1

Z1

Z2

Z3

Z4

Z5