D-2

Compact NS630b to 1600

Fixed circuit breakers

The diagram is shown with circuits de-energised,

all devices open, connected and charged and relays

in the normal position.

E; energy

A : digital ammeter.

P : A + power meter + additional protection.

Power

Control unit

Remote operation

DB128378

Power

Upstream cb Downstream cb

24 V DC

Q

Micrologic

M6C

M1

M2

T3

F2+

T2

T1/M3

T4/F1

VN

Z1

Z2

Z3

Z4

Z5

Z1

Z2

Z3

Z4

Z5

Z1

Z2

Z3

Z4

Z5

Q1

Q2

Q3

L2 L3

L1 N

DB128373

or

AT

BPO BPF

MN MX

D2

A2

A4

B4

C2

D1

1A

1C

Motor-mechanism

module

Basic A E P Control unit

Remote operation

b

b b b

E1-E6 communication

b b b

Z1-Z5 zone selective interlocking:

Z1 = ZSI OUT SOURCE

Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE

Z4 = ZSI IN ST (short time)

Z5 = ZSI IN GF (earth fault)

b

b

M1 = Vigi module input

(Micrologic 7)

b b b

T1, T2, T3, T4 = external neutral;

b

M2, M3 = Vigi module input

(Micrologic 7)

b b b

F2+, F1– external 24 V DC

power supply

b b

VN external voltage connector

(must be connected to the neutral

with a 3P circuit breaker)

b

M6C

: 6 programmable contacts (to

be connected to the external module

M6C) ext. 24 V DC power supply

required

MN

:

undervoltage release

or

MX

:

shunt release

Motor-mechanism module

(*)

A4

:

electrical opening order

A2

:

electrical closing order

B4, A1

:

power supply for control devices and gear motor

(*) Spring-charging motor 440/480 V AC

(380 V motor + additional resistor)

DB128380

A1

CN2

a

- 440/480 V

9 11

B4

R

A2

A4

CN1

a

- 440/480 V

Motor-mechanism

module

Electrical diagrams