Background Image
Table of Contents Table of Contents
Previous Page  125 / 148 Next Page
Information
Show Menu
Previous Page 125 / 148 Next Page
Page Background

C-26

Power connections for

Compact NS630b to 3200

Sizing of bars

Compact

Maximum T

i

: 40 °C

T

i

: 50 °C

T

i

: 60 °C

service Number of bars

Number of bars

Number of bars

current

5 mm thick 10 mm thick 5 mm thick

10 mm thick

5 mm thick

10 mm thick

NS630b

400

2b.30 x 5

1b.30 x 10 2b.30 x 5

1b.30 x 10

2b.30 x 5

1b.30 x 10

NS630b

630

2b.40 x 5

1b.40 x 10 2b.40 x 5

1b.40 x 10

2b.40 x 5

1b.40 x 10

NS800

800

2b.50 x 5

1b.50 x 10 2b.50 x 5

1b.50 x 10

2b.50 x 5

1b.63 x 10

NS1000

1000

3b.50 x 5

1b.63 x 10 3b.50 x 5

2b.50 x 10

3b.63 x 5

2b.50 x 10

NS1250

1250

3b.50 x 5

2b.40 x 10 3b.50 x 5

2b.50 x 10

3b.63 x 5

2b.50 x 10

2b.80 x 5

2b.40 x 10 2b.80 x 5

NS1600/1600b 1400

2b.80 x 5

2b.40 x 10 2b.80 x 5

2b.50 x 10

3b.80 x 5

2b.63 x 10

NS1600/1600b 1600

3b.80 x 5

2b.63 x 10 3b.80 x 5

2b.63 x 10

3b.80 x 5

3b.50 x 10

NS2000

1800

3b.80 x 5

2b.63 x 10 3b.80 x 5

2b.63 x 10

3b.100 x 5

2b.80 x 10

NS2000

2000

3b.100 x 5

2b.80 x 10 3b.100 x 5

2b.80 x 10

3b.100 x 5

3b.63 x 10

NS2500

2200

3b.100 x 5

2b.80 x 10 3b.100 x 5

2b.80 x 10

4b.80 x 5

2b.100 x 10

NS2500

2500

4b.100 x 5

2b.100 x 10 4b.100 x 5

2b.100 x 10

4b.100 x 5

3b.80 x 10

NS3200

2800

4b.100 x 5

3b.80 x 10 4b.100 x 5

3b.80 x 10

5b.100 x 5

3b.100 x 10

NS3200

3000

5b.100 x 5

3b.80 x 10 6b.100 x 5

3b.100 x 10

8b.100 x 5

4b.80 x 10

NS3200

3200

6b.100 x 5

3b.100 x 10 8b.100 x 5

3b.100 x 10

4b.100 x 10

Note.

With Compact NS630b to NS1600, it is recommended to use 50 mm wideness bars (see "Recommended busbars drilling").

The following tables are based on the following assumptions:

maximum permissible temperature of bars is 100 °C

b

Ti: temperature around the circuit breaker and its connections

b

busbars made of copper and not painted.

b

Note.

The values presented in the tables are the result of trials and theoretical calculations on the basis

of the assumptions mentioned above.

These tables are intended as an aid in designing connections, however, the actual values must

be confirmed by tests on the installation.

Front or horizontal rear connections

DB128370

Dimensions

and connection