iPRD surge arresters

Type 2 or 3 LV withdrawable surge arresters (cont.)

Protection

Load protection

Technical data

Main characteristics

Operating frequency

50/60 Hz

Operating voltage (Ue)

230/400 V AC ±10 %

Permanent operating current (Ic)

< 1 mA

Response time

< 25 ns

Short circuit withstand (Isccr)

50 kA (50 Hz)

Temporary overvoltage withstand (U

T

)

U

T

(L-N)

337 V AC / 5 s

U

T

(L-PE)

442 V AC / 5 s

Temporary overvoltage

Safe failure mode

(U

T

)

U

T

(N-PE)

1200 V AC / 200 ms

U

T

(L-PE)

1453 V AC / 200 ms

Ground residual current (I

PE

)

I

PE

(N-PE)

3 μA for 1P+N, 3P+N

Satisfactory operation indication: by

mechanical indicator

White

In operation

Red

Cartridge must be replaced

Remote indication of satisfactory operation

By contact NO, NC 250 V / 0.25 A

Additional characteristics

Degree of protection (IEC 60529)

Device only

IP20 (built-in)

Device in modular

enclosure

IP40

Operating temperature

-25°C to +60°C

Humidity range

5 % to 95 %

Type of connection terminals

Tunnel terminals, 2.5 to 35 mm²

Standards

IEC 61643-11: 2011

T2

,

T3

and

EN 61643-11: 2012 Type 2, Type 3

Surge arrester/circuit breaker association

Type of surge arrester

Associated circuit breaker

(1 to 4 poles protected)

iPRD65

Curve C 50 A

iPRD40

Curve C 40 A

iPRD20

Curve C 25 A

iPRD8

Curve C 20 A

Connection

DB123130

Type

Tightening torque

Copper cables

Rigid

Flexible or with ferrule

iPRD

3.5 N.m

2.5 to 25 mm

2

4 to 16 mm

2

6.5mm

14mm

PZ2

IP20

IP40

DB122945

DB122946

DB123314