4/16
Technical
Section 11
Dimensions
Section 12
4
10 m
iPRD-DC
1
10 m
iPRD-DC
1
iPRD-DC
2
Generator
Conversion
Generator
Conversion
Depending on the distance between the "generator" part and the "conversion" part,
it may be necessary to install two surge arresters or more, to ensure protection of
each of the two parts.
Connection
DB124057
Type
Tightening torque Copper cables
Rigid
Flexible or ferrule
iPRD-DC
2 N.m
2.5 to 25 mm
2
2.5 to 16 mm
2
6.5 mm
14 mm
PZ2
DB122945
DB122946
DB124049
iPRD-DC surge arresters
Withdrawable surge arresters type 2 for
photovoltaic applications (cont.)
Protection
Load protection