iPRD surge arresters

Type 2 or 3 LV withdrawable surge arresters (cont.)

Protection

Load protection

4P

2P

Catalogue number iPRD surge arresters

Rated discharge

current (Imax)

Nominal

discharge

current (In)

Type of protection Network

Incoming Secondary 1P+N

3P+N

iPRD65

65 kA

Very high risk level

(strongly exposed site)

20 kA

iPRD65

A9L65501

A9L65601

iPRD40

40 kA

High risk level

15 kA

iPRD40

A9L40501

A9L40500

A9L40601

A9L40600

iPRD20

20 kA

Medium risk level

5 kA

iPRD20

A9L20501

A9L20500

A9L20601

A9L20600

iPRD8

8 kA

Secondary protection:

placed near the loads to

be protected when they

are at a distance of more

than 10 m from the

incoming surge arrester

2.5 kA

iPRD8

A9L08501

A9L08500

A9L08601

A9L08600

iPRD withdrawable surge arresters allow quick

replacement of damaged cartridges.

Type 2 surge arresters are tested with a 8/20 μs current

wave.

Type 3 surge arresters are tested with a 1.2/50 μs and

8/20 μs combined wave.

Each surge arrester in the range has a specific application:

b

b

incoming protection (type 2):

v

v

the iPRD65r is recommended for a very high risk level (strongly exposed site)

v

v

the iPRD40(r) is recommended for a high risk level

v

v

the iPRD20(r) is recommended for a medium risk level

b

b

secondary protection (type 2 or 3):

v

v

the iPRD8(r) ensures secondary protection of loads to be protected and is placed

in cascade with the incoming surge arresters. This surge arrester is required when

the loads to be protected are at a distance of more than 10 m from the incoming

surge arrester.

The iPRD surge arresters with “r” indication have remote transfer of the information:

“cartridge to be replaced”.

DB123854

DB106604

e