Background Image
Table of Contents Table of Contents
Previous Page  75 / 408 Next Page
Information
Show Menu
Previous Page 75 / 408 Next Page
Page Background

3/25

Technical

Section 11

Dimensions

Section 12

3

P25M (cont.)

Load protection

Motor starter protection

Technical data

Electrical characteristics

Operating voltage (Ue)

690 V AC

Insulation voltage (Ui)

690 V

Rated impulse withstand voltage (Uimp)

6 kV

Endurance (O-C)

Electrical AC3

100,000 cycles

Thermal trip unit

Sensitive to missing phase

Settings

Factory < settings range

Simultaneously on the front face

On current drawn in nominal operation

Ratings (In)

0.16 to 25 A adjustable

Temperature

compensation

-20°C to +40 °C in an enclosure

Magnetic trip unit

12 x the In rating (±20 %)

Other characteristics

Padlocking device on the front face

Tropicalisation

Treatment 2 (relative humidity 95 % at 55°C)

Operating temperature

-20 ...+60°C

Storage temperature

-40 ...+80°C

Connection

P25M

Limiting unit

DB125904

PZ2

5.5 mm

Tightening

torque

Terminal clamps

With insulated

connector

Tunnel terminals

Rigid Cu

Flexible Cu

Flexible Cu

Flexible or rigid Cu

1.7 N.m.

2 x 1 ... 6 mm

2

2 x 1.5 ... 6 mm

2

1 x 25 mm

2

or 2 x 10 mm

2

DB118767

Mounted on 35 mm DIN rail.

DB126273

0...90°

0...30°

DB122932

DB126274

Dimensions (mm)

010-0100

DB126275

013-0100

Circuit breaker

Limiting unit only

Insulating enclosure

IP20

IP40

Weight (g)

P25M

260

Limiting unit

130

Rated operating current (Ie) of auxiliary contacts under the rated operating voltage (Ue)

Operating voltage (Ue)

Operating current

Position contact

fault tripping contact

AC 15

DC 13

AC 14

DC 13

(V AC)

(V DC)

(A AC)

(A DC)

(A AC)

(A DC)

415

220

2.2

0.5

-

-

240

110

3.3

1.3

-

-

130

60

4.5

3

0.5

0.15

48

48

6

5

1

0.3

24

24

-

6

1.5

1