Load protection
Motor starter protection
Technical data
Electrical characteristics
Operating voltage (Ue)
690 V AC
Insulation voltage (Ui)
690 V
Rated impulse withstand voltage (Uimp)
6 kV
Endurance (O-C)
Electrical AC3
100,000 cycles
Thermal trip unit
Sensitive to missing phase
Settings
Factory < settings range
Simultaneously on the front face
On current drawn in nominal operation
Ratings (In)
0.16 to 25 A adjustable
Temperature
compensation
-20°C to +40 °C in an enclosure
Magnetic trip unit
12 x the In rating (±20 %)
Other characteristics
Padlocking device on the front face
Tropicalisation
Treatment 2 (relative humidity 95 % at 55°C)
Operating temperature
-20 ...+60°C
Storage temperature
-40 ...+80°C
Connection
P25M
Limiting unit
DB125904
PZ2
5.5 mm
Tightening
torque
Terminal clamps
With insulated
connector
Tunnel terminals
Rigid Cu
Flexible Cu
Flexible Cu
Flexible or rigid Cu
1.7 N.m.
2 x 1 ... 6 mm
2
2 x 1.5 ... 6 mm
2
1 x 25 mm
2
or 2 x 10 mm
2
DB118767
Mounted on 35 mm DIN rail.
DB126273
0...90°
0...30°
DB122932
DB126274
Dimensions (mm)
010-0100
DB126275
013-0100
Circuit breaker
Limiting unit only
Insulating enclosure
IP20
IP40
Weight (g)
P25M
260
Limiting unit
130
Rated operating current (Ie) of auxiliary contacts under the rated operating voltage (Ue)
Operating voltage (Ue)
Operating current
Position contact
fault tripping contact
AC 15
DC 13
AC 14
DC 13
(V AC)
(V DC)
(A AC)
(A DC)
(A AC)
(A DC)
415
220
2.2
0.5
-
-
240
110
3.3
1.3
-
-
130
60
4.5
3
0.5
0.15
48
48
6
5
1
0.3
24
24
-
6
1.5
1