3/24
Technical
Section 11
Dimensions
Section 12
3
P25M
Load protection
Motor starter protection
(1) The neutral pole comes equipped with a locked tube.
IEC60947-2 and IEC60947-4-1 (in combination)
They protect single-phase or three-phase motors with manual local control.
This protection includes:
b
b
isolation
b
b
manual or remote control
b
b
short-circuit protection (magnetic)
b
b
overload protection (thermal).
Breaking capacity to IEC 60947-2
Voltage (V)
230...240
400...415
440
500
690
Rating (A) Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
kA % kA % kA % kA % kA %
0.16 to 1.6
Unlimited
2.5
3
75
4
3
75
6.3
50 100 50 100 3
75
10
15 100 10 100 3
75
14
15 50 8
50 6
75 3
75
18
15 50 8
50 6
75 3
75
23
50 100 15 40 6
50 4
75 3
75
25
50 100 15 40 6
50 4
75 3
75
The limiting unit increases the breaking capacity up to 100 kA at 415 V.
Motor characteristics
P25M circuit breaker
Type
Standardised power (kW) of three-phase 50/60 Hz motors in category AC3
Rating In
(A)
Setting
Cat. no.
Width in
9 mm
modules
Voltage (V AC)
230
400
415
440
500
690
3P
1
2
3
4
5
6
-
-
-
-
-
-
0.16
0.1-0.16
21100
5
-
-
-
-
-
-
0.25
0.16-0.25
21101
5
-
-
-
-
-
-
0.40
0.25-0.40
21102
5
-
-
-
-
-
0.37
0.63
0.40-0.63
21103
5
-
-
-
0.37
0.37
0.55
1.0
0.63-1
21104
5
-
0.37
-
0.55
0.75
1.1
1.6
1-1.6
21105
5
0.37
0.75
1.1
1.1
1.1
1.5
2.5
1.6-2.5
21106
5
0.75
1.5
1.5
1.5
2.2
3
4.0
2.5-4
21107
5
1.1
2.2
2.2
3
3.7
4
6.3
4-6.3
21108
5
2.2
4
4
4
5;5
7.5
10
6-10
21109
5
3
5.5
5.5
7.5
9
11
14
9-14
21110
5
4
7.5
9
9
10
15
18
13-18
21111
5
5.5
9
11
11
11
18.5
23
17-23
21112
5
5.5
11
11
11
15
22
25
20-25
21113
5
Limiting unit
Type
Rating In
(A)
Cat. no.
Width in 9 mm
modules
3P
63
21115
5
045666_SE
E12648C
PG131075_SE
Catalogue numbers